ELECTRICAL WIRING WORKPreparation of indoor unitMounting of connecting wires1234567Open the air inlet panel.Remove the lid.Remove the wiring clamp.Connect the connecting wire securely to the terminal block.1) Connect the connection wire securely to the terminalblock. If the wire is not affixed completely, contact will bepoor, and it is dangerous as the terminal block may heatup and catch fire.2) Take care not to confuse the terminal numbers for indoorand outdoor connections.Fix the connecting wire by wiring clamp.Attach the lid.Close the air inlet panel.CAUTIONIn case of faulty wiring connection, the indoor unit stops, andthen the run lamp turns on and the timer lamp blinks.Use cables for interconnection wiring to avoid loosening of thewires.CENELEC code for cables Required field cables.H05RNR4G1.5 (example) or 245IEC57H Harmonized cable type05 300/500 voltsR Natural-and/or synth, rubber wire insulationN Polychloroprene rubber conductors insulationR Stranded core4or5 Number of conductorsG One conductor of the cable is the earth conductor(yellow/green)1.5 Section of copper wire (mm 2 )Terminal block1 2 N 3Wiring ClampLidInstalling the air-cleaning filters1. Open the air inlet panel and remove the air filters.2. Install the filter holders, with the air-cleaning filters installed in the holders.In the air conditioner.• Each air-cleaning filter can be installed in the left or right filter holder.3. Install the air filters and close the inlet panel.Air-cleaningfilterFilter holderINSTALLATION OF WIRELESS CONTROLMounting method of battery Uncover the wireless remote control, and mount the batteries[R03 (AAA, Micro), 2 pieces] in the body regularly.(Fit the poles with the indication marks, & without fail)CAUTIONDo not use new andold batteries together.6 BatteryCoverFixing to pillar or wall Conventionally, operate the wireless remote control by holdingin your hand. Avoid installing it on a clay wall etc.2 Wireless remote control5 Wood screwsø3.5 X 16INSTALLATION TEST CHECK POINTSCheck the following points again after completion of the installation, and before turning on the power. Conduct a test run again and ensure that the unit operates properly.At the same time, explain to the customer how to use the unit and how to take care of the unit following the user’s manual.After installationThe power supply voltage is correct as the rating.No gas leaks from the joints of the operation valve.Power cables and crossover wires are securely fixed to the terminal board.Operation valve is fully open.The pipe joints for indoor and outdoor pipes have been insulated.Test runAir conditioning operation is normal.Operation of the unit has been explained to the customer.No abnormal noise.(Three-minutes restart preventive timer)Water drains smoothly.When the air conditioner is restarted or when changing the operation, the unitProtective functions are not working.will not start operating for approximately 3 minutes.The remote control is normal.This is to protect the unit and it is not a malfunction.HOW TO RELOCATE OR DISPOSE OF THE UNIT In order to protect the environment, be sure to pump down (recovery of refrigerant). Pump down is the method of recovering refrigerant from the indoor unit to theoutdoor unit when the pipes are removed from the unit.1 Connect charge hose to check joint of outdoor unit.2 Liquid side : Close the liquid valve with hexagon wrench key.Gas side : Fully open the gas valve.Carry out cooling operation. (If indoor temperature is low, operateforced cooling operation.)3 After low pressure gauge become 0.01MPa, stop cooling operationand close the gas valve.• Forced cooling operationTurn on a power supply again after a while after turn off a power supply.Then press continually the ON/OFF button 5 seconds or more.Unit ON/OFF button- 31 - '11 • SRK-T-105CONCERNING TERMINAL CONNECTION FOR AN INTERFACE1 Remove the air inlet panel, lid and front panel.2 Remove the control cover. (Remove the screw.)3 There is a terminal (respectively marked with CNS) for the indoor control board.In connecting an interface, connect to the respective terminal securely with the connection harnesssupplied with an optional “Interface connection kit SC-BIKN-E” and fasten the connection harnessonto the indoor control box with the clamp supplied with the kit.For more details, please refer to the user’s manual of your “Interface connection kit SC-BIKN-E”.Indoor unit PCBScrewControl coverCNS terminal
(2) Installation of outdoor unitModels SRC63ZK-S, 71ZK-S, 80ZK-SRCR012A001• Read the “SAFETY PRECAUTIONS” carefully first of all and strictly follow it during the installation work in orderto protect yourself.• The precautionary items mentioned below are distinguished into two levels, WARNING and CAUTION .WARNING : Wrong installation would cause serious consequences such as injuries or death.CAUTION : Wrong installation might cause serious consequences depending on circumstances.Both mentions the important items to protect your health and safety so strictly follow them by any means.• Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain theoperating methods as well as the maintenance methods of this equipment to the user according to the owner’smanual.R410A REFRIGERANT USED• This installation manual deals with outdoor units and general installation specifications only. For indoor units, refer to page 19.• When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height differences between indoor and outdoor units, powersupply voltage and etc.) and installation spaces.SAFETY PRECAUTIONS• Keep the installation manual together with owner’s manual at a place where any user can read at any time.Moreover if necessary, ask to hand them to a new user.• For installing qualified personnel, take precautions in respect to themselves by using suitable protectiveclothing, groves, etc., and then perform the installation works.• Please pay attention not to fall down the tools, etc. when installing the unit at the high position.• If unusual noise can be heard during operation, consult the dealer.• The meanings of “Marks” used here are as shown on the right:Never do it under any circumstances.Always do it according to the instruction.• Installation must be carried out by the qualified installer.If you install the system by yourself, it may cause serious trouble such as waterleaks, electric shocks, fire and personal injury, as a result of a system malfunction.• Install the system in full accordance with the installation manual.Incorrect installation may cause bursts, personal injury, water leaks, electricshocks and fire.• Be sure to use only for household and residence.If this appliance is installed in inferior environment such as machine shop and etc.,it can cause malfunction.• When installing in small rooms, take prevention measures not toexceed the density limit of refrigerant in the event of leakage, referredby the formula (accordance with ISO5149).If the density of refrigerant exceeds the limit, please consult the dealer and installthe ventilation system, otherwise lack of oxygen can occur, which can cause seriousaccident.• Use the original accessories and the specified components forinstallation.If parts other than those prescribed by us are used, It may cause water leaks,electric shocks, fire and personal injury.• Install the unit in a location with good support.Unsuitable installation locations can cause the unit to fall and cause materialdamage and personal injury.• Ensure the unit is stable when installed, so that it can withstandearthquakes and strong winds.Unsuitable installation locations can cause the unit to fall and cause materialdamage and personal injury.WARNING• Ventilate the working area well in the event of refrigerant leakage duringinstallation.If the refrigerant comes into contact with naked flames, poisonous gas is produced.• Use the prescribed pipes, flare nuts and tools for R410A.Using existing parts (for R22 or R407C) can cause the unit failure and seriousaccidents due to burst of the refrigerant circuit.• Tighten the flare nut by torque wrench with specified method.If the flare nut were tightened with excess torque, this may cause burst andrefrigerant leakage after a long period.• Do not open the operation valves for liquid line and gas line untilcompleted refrigerant piping work, air tightness test and evacuation.If the compressor is operated in state of opening operation valves beforecompleted connection of refrigerant piping work, air can be sucked into refrigerantcircuit, which can cause bust or personal injury due to anomalously high pressurein the refrigerant.• The electrical installation must be carried out by the qualified electricianin accordance with “the norm for electrical work” and “national wiringregulation”, and the system must be connected to the dedicated circuit.Power supply with insufficient capacity and incorrect function done by improperwork can cause electric shocks and fire.• Be sure to shut off the power before starting electrical work.Failure to shut off the power can cause electric shocks, unit failure or incorrectfunction of equipment.• Be sure to use the cables conformed to safety standard and cableampacity for power distribution work.Unconformable cables can cause electric leak, anomalous heat production or fire.• This appliance must be connected to main power supply by means of acircuit breaker or switch (fuse:20A) with a contact separation of at least3mm.• Arrange the wiring in the control box so that it cannot be pushed upfurther into the box. Install the service panel correctly.Incorrect installation may result in overheating and fire.• Use the prescribed cables for electrical connection, tighten the cablessecurely in terminal block and relieve the cables correctly to preventoverloading the terminal blocks.Loose connections or cable mountings can cause anomalous heat production orfire.• Be sure to fix up the service panels.Incorrect fixing can cause electric shocks or fire due to intrusion of dust or water.• Be sure to switch off the power supply in the event of installation,inspection or servicing.If the power supply is not shut off, there is a risk of electric shocks, unit failure orpersonal injury due to the unexpected start of fan.• Stop the compressor before removing the pipe after shutting theservice valve on pump down work.If the pipe is removed when the compressor is in operation with the service valveopen, air would be mixed in the refrigeration circuit and it could cause explosionand injuries due to abnormal high pressure in the cooling cycle.• Only use prescribed optional parts. The installation must be carried outby the qualified installer.If you install the system by yourself, it can cause serious trouble such as waterleaks, electric shocks, fire.- 32 - '11 • SRK-T-105• Ensure that no air enters in the refrigerant circuit when the unit is • Do not bundling, winding or processing for the power cord. Or, do notinstalled and removed.deforming the power plug due to tread it.If air enters in the refrigerant circuit, the pressure in the refrigerant circuitThis may cause fire or heating.becomes too high, which can cause burst and personal injury.• Do not run the unit with removed panels or protections.• Do not processing, splice the power cord, or share a socket with other power plugs. Touching rotating equipments, hot surfaces or high voltage parts can causeThis may cause fire or electric shock due to defecting contact, defecting insulation personal injury due to entrapment, burn or electric shocks.and over-current etc.• Do not perform any change of protective device itself or its setupcondition.The forced operation by short-circuiting protective device of pressure switch andtemperature controller or the use of non specified component can cause fire orburst.