2 TECHNICAL DATAExplosion protectiona) Fitted with terminalsb) Fitted with isolating terminalsc) Fitted with terminals and fusesd) Fitted with terminals, isolating terminals andfusesII 2G Ex e II TEx e ia/ib II T. , Ex ia/ib IIC T.II 2G Ex ed IIC T.II 2G Ex em II T.II 2G Ex edm IIC T.e) Terminal boxes for dust environmentII 2D Ex tb IIIA T.Test certificate KEMA 03 ATEX 2139Degree of protection to IEC/CEI 60529 max. IP 66Terminal box Ex e type <strong>KKE</strong>Rated operating voltageCross-section for connectionMax. 1100 VMax. 300 mm²Terminal box Exi type <strong>KKE</strong>The electrical data depend on the rated operatingvalues of the intrinsically safe circuits installed.Temperature rangeStandardSpecialAmbient temperature range for terminal boxeswithout fuses fitted- 33 °C ... + 40 °C- 33 °C ... + 55 °C, -50°C … + 200°CT6: - 33 °C ... + 40 °CT5: - 33 °C ... + 55 °CT3: + 200 °CIf your application requires the ambient temperature range to be extended at the lower end, <strong>Electromach</strong>can supply special designs.PAGE 6/ 13