fire protection products – firelock automatic sprinklersFireLock ® LP-<strong>46</strong> Low Pressure <strong>Storage</strong> <strong>Sprinkler</strong>Model LP-<strong>46</strong> (SIN) V<strong>46</strong>03, K25.2, Standard Response <strong>Storage</strong> Upright <strong>Sprinkler</strong>MODEL LP-<strong>46</strong><strong>40.98</strong>approvals/listingsModelNominalK-Factor Response Deflector TypeFM Approved TemperatureRatings ‡V<strong>46</strong>03ImperialS.I.^25.236.8StandardUpright162 º F/72 º C212 º F/100 º C286 º F/141 º C^ For K-Factor when <strong>pressure</strong> is measured in Bar, multiply S.I. units by 10.0.‡ Listings and approvals as of printing.temperature ratingsUse the nominally rated 162°F/72°C sprinkler for all acceptable applications on a wet-typesprinkler system unless the ambient temperature of the protected occupancy requires the nominaltemperature rating to be 212°F/100°C. The nominally rated, 286ºF/141ºC sprinkler is required forall acceptable dry-type applications and can also be used on applicable wet type systems, whenrequired.All links are rated for temperatures from -67°F/-55°C to those shown in table be<strong>low</strong>.Temperature – ºF/ºC<strong>Sprinkler</strong>TemperatureClassificationOrdinaryIntermediateHigh<strong>Victaulic</strong>PartIdentificationNGJNominal TemperatureRatingMaximum AmbientTemperature Al<strong>low</strong>ed162 10072 3821210028614115065225107Link ColorBlack/NoneBlack with White Dot/White armsBlack with Blue DotSYSTEM DESIGN ANDLISTING REQUIREMENTSPER FM GLOBALLOSS PREVENTION RECOMMENDATIONSFor wet systems up to 40 ft/12.2m and dry systems up to 30 ft/9.1m, and dry systems over 30ft/9.1m, see FM Data Sheet 8-9. Ensure the required <strong>pressure</strong> is reached and maintained within thetime frame mandated by FM Global.Install the <strong>Victaulic</strong> V<strong>46</strong>03 upright automatic sprinkler in accordance with the fol<strong>low</strong>ing guidelines:TABLE ONELP-<strong>46</strong> Upright (V<strong>46</strong>03) for Wet SystemsClass I - IV and Cartoned Unexpanded Group A PlasticSolid-Piled, Palletized, Shelf or Bin-Box arrangementsWithout Need for In-Rack <strong>Sprinkler</strong>s<strong>Storage</strong> Up To:Number of <strong>Sprinkler</strong>s 24*Up to 40ft/12.2m Discharge Pressure (psi/kPa) 15/103*high ceiling and up to35ft/10.7m high storage System Demand (gpm/<strong>lp</strong>m) 2342/8865*Hose Stream Demand 500gpm(1893<strong>lp</strong>m)/120minNumber of <strong>Sprinkler</strong>s 15*Up to 35ft/10.7m high Discharge Pressure (psi/kPa) 15/103*ceiling and up to25ft/7.6m high storage System Demand (gpm/<strong>lp</strong>m) 1<strong>46</strong>4/5542*Hose Stream Demand 500gpm(1893<strong>lp</strong>m)/90minNumber of <strong>Sprinkler</strong>s 12Up to 30ft/9.1m high Discharge Pressure (psi/kPa) 20/138ceiling and up to15 ft/4.6m high storage System Demand (gpm/<strong>lp</strong>m) 1352/5118Hose Stream Demand 250gpm(9<strong>46</strong><strong>lp</strong>m)/60min* Up to Class III Commodities onlyData based upon FM Global Loss Prevention Data Sheet 8-910ft x 10ft/3m x 3m deflector spacing, 12"/305mm thermal element to ceilingdistancewww.victaulic.com<strong>Victaulic</strong> is a registered trademark of <strong>Victaulic</strong> Company. © 2013 <strong>Victaulic</strong> Company. All rights reserved.<strong>40.98</strong>_2REV_G


fire protection products – firelock automatic sprinklers<strong>40.98</strong>FireLock ® LP-<strong>46</strong> Low Pressure <strong>Storage</strong> <strong>Sprinkler</strong>Model LP-<strong>46</strong> (SIN) V<strong>46</strong>03, K25.2, Standard Response <strong>Storage</strong> Upright <strong>Sprinkler</strong>MODEL LP-<strong>46</strong>SYSTEM DESIGN ANDLISTING REQUIREMENTSPER FM GLOBALTABLE TWOLP-<strong>46</strong> Upright (V<strong>46</strong>03) for Wet SystemsClass I-IV and Cartoned Unexpanded Group A PlasticSolid-Piled, Palletized, Shelf or Bin-Box ArrangementsOpen Frame Rack <strong>Storage</strong> Arrangements Without Need for In-Rack <strong>Sprinkler</strong>s<strong>Storage</strong> Up To:Number of <strong>Sprinkler</strong>s 24*Up to 40ft/12.2m Discharge Pressure (psi/kPa) 15/103*high ceiling and up to35ft/10.7m high storage System Demand (gpm/<strong>lp</strong>m) 2342/8865*Hose Stream Demand 500gpm(1993<strong>lp</strong>m)/120minNumber of <strong>Sprinkler</strong>s 12Up to 30ft/9.1m Discharge Pressure (psi/kPa) 20/138high ceiling and up to25ft/7.6m high storage System Demand (gpm/<strong>lp</strong>m) 1352/5118Hose Stream Demand 250gpm(9<strong>46</strong><strong>lp</strong>m)/60min* Up To Class III Commodities OnlyTABLE THREELP-<strong>46</strong> Upright (V<strong>46</strong>03) for Refrigerated and FreezerDry/Preaction SystemsClass I - III Commodity <strong>Storage</strong>Solid-Piled, Palletized, Shelf or Bin-Box arrangements without need for in-rack sprinklers<strong>Storage</strong> Up To:Up to 45ft/13.7m highceiling and up to40ft/12.2m high storageUp to 40ft/12.2mhigh ceiling and up to35ft/10.7m high storageUp to 35ft/10.7m highceiling and up to30ft/9.1m high storageNumber of <strong>Sprinkler</strong>s 12*Discharge Pressure (psi/kPa) 50/345*System Demand (gpm/<strong>lp</strong>m) 2140/8101*Hose Stream Demand 500gpm(1893<strong>lp</strong>m)/90minNumber of <strong>Sprinkler</strong>s 24**Discharge Pressure (psi/kPa) 15/103**System Demand (gpm/<strong>lp</strong>m) 2342/8865**Hose Stream Demand 500gpm(1893<strong>lp</strong>m)/120minNumber of <strong>Sprinkler</strong>s 20Discharge Pressure (psi/kPa) 7/48System Demand (gpm/<strong>lp</strong>m) 1333/50<strong>46</strong>Hose Stream Demand 500gpm(1893<strong>lp</strong>m)/120min* Based upon water delivery of 20 seconds or less** Based upon water delivery of 25 seconds or lessData based upon FM Global Loss Prevention Data Sheet 8-910ft x 10ft/3m x 3m deflector spacing, 12"/305mm thermal element to ceilingdistancewww.victaulic.com<strong>Victaulic</strong> is a registered trademark of <strong>Victaulic</strong> Company. © 2013 <strong>Victaulic</strong> Company. All rights reserved.REV_G<strong>40.98</strong>_3


fire protection products – firelock automatic sprinklers<strong>40.98</strong>FireLock ® LP-<strong>46</strong> Low Pressure <strong>Storage</strong> <strong>Sprinkler</strong>Model LP-<strong>46</strong> (SIN) V<strong>46</strong>03, K25.2, Standard Response <strong>Storage</strong> Upright <strong>Sprinkler</strong>MODEL LP-<strong>46</strong>SYSTEM DESIGN ANDLISTING REQUIREMENTSPER FM GLOBALTABLE FOURLP-<strong>46</strong> Upright (V<strong>46</strong>03) for Refrigerated and Freezer Dry/Preaction SystemsClass I - III Commodity <strong>Storage</strong>Open Frame Rack <strong>Storage</strong> after arrangements without need for in-rack sprinklers<strong>Storage</strong> Up To:Number of <strong>Sprinkler</strong>s 12*Up to 45ft/13.7m high Discharge Pressure (psi/kPa) 50/345*ceiling and up to40ft/12.2m high storage System Demand (gpm/<strong>lp</strong>m) 2140/8101*Hose Stream Demand 500gpm(1893<strong>lp</strong>m)/90minNumber of <strong>Sprinkler</strong>s 24**Up to 40ft/12.2m Discharge Pressure (psi/kPa) 15/103**high ceiling and up to35ft/10.7m high storage System Demand (gpm/<strong>lp</strong>m) 2342/8865**Hose Stream Demand 500gpm(1893<strong>lp</strong>m)/120minNumber of <strong>Sprinkler</strong>s 25up to 30ft/9.1m high Discharge Pressure (psi/kPa) 10/69ceiling and up to25ft/7.6m high storage System Demand (gpm/<strong>lp</strong>m) 1992/7541Hose Stream Demand 500gpm(1893<strong>lp</strong>m)/120min* Based upon water delivery of 20 seconds or less** Based upon water delivery of 25 seconds or lessData based upon FM Global Loss Prevention Data Sheet 8-910ft x 10ft/3m x 3m deflector spacing, 12"/305mm thermal element to ceilingdistance.Note: The water delivery time needs to be confirmed via an analysis by Engineering Standards ora software program listed in the Specification Tested Product section of the Approval Guide, anonline resource of FM Approvals. If confirmed by the software program, base the sprinkler operationsequence on the simultaneous opening of the four most-remote sprinklers (two sprinklers on twolines).Number of <strong>Sprinkler</strong>s*Operating Area and Hose Stream Demand RequirementsHose Demand(gpm/<strong>lp</strong>m)Duration(minutes)12** 250/9<strong>46</strong> 6013-15** 500/1893 9016 500/1893 120* One sprinkler for every 100 sq ft/9.3 sq m** For ceiling heights above 35 ft/10.7m, up to 45ft/13.7m, if using the 12 sprinklers for50psi/345kPa discharge <strong>pressure</strong> design criteria, Hose Demand requirement is500gpm/1893<strong>lp</strong>m for 90 minutes.Data based upon FM Global Loss Prevention Data Sheet 8-9The sprinkler can also be used to protect portable rack storage if the portable racks meet therequirements for them to be considered open-frame racks (see DS 8-9, <strong>Storage</strong> of Class I - IV andPlastic Commodities). For all storage arrangements, maintain a minimum 3 ft (0.9 m) clearancebetween the top of storage and the sprinkler deflector.Commodity Hazards Other Than Class I- IV and Cartoned Plastics: The <strong>Victaulic</strong> V<strong>46</strong>03 K25.2(K360) upright sprinkler can be used to protect any commodity hazard that can be protected by theK11.2 (K160) upright CMSA sprinkler. Base the design for the K25.2 (K360) upright sprinkler usingthe same design required for the K11.2 (K160) sprinkler, however base the required <strong>pressure</strong> usingthe fol<strong>low</strong>ing chart.Commodities other than Class I-IV and Cartoned PlasticsDesign Pressure of K11.2 (K160) CMSAStandard Response Upright <strong>Sprinkler</strong>*psi/kPaCorresponding Design Pressure of LP-<strong>46</strong>K25.2 (K360) Standard Response Upright<strong>Sprinkler</strong>*psi/kPaUp to 25/170 7/48Over 25/170 up to 50/350 10/69Over 50/350 up to 75/520 10/69* One sprinkler for every 100 sq. ft/9.29 sq. mData based upon FM Global Loss Prevention Data Sheet 8-9www.victaulic.com<strong>Victaulic</strong> is a registered trademark of <strong>Victaulic</strong> Company. © 2013 <strong>Victaulic</strong> Company. All rights reserved.<strong>40.98</strong>_4REV_G


fire protection products – firelock automatic sprinklersFireLock ® LP-<strong>46</strong> Low Pressure <strong>Storage</strong> <strong>Sprinkler</strong>Model LP-<strong>46</strong> (SIN) V<strong>46</strong>03, K25.2, Standard Response <strong>Storage</strong> Upright <strong>Sprinkler</strong>MODEL LP-<strong>46</strong><strong>40.98</strong>SYSTEM DESIGN ANDLISTING REQUIREMENTSPER FM GLOBALShape of Operating Area: This sprinkler is not permitted in buildings having a ceiling slope over 10°unless the ceiling sprinkler is supplemented with in-rack sprinkler protection. Base the number ofsprinklers in the Operating Area parallel to the branchline based on the fol<strong>low</strong>ing equation:Number of AS in operating area parallel to branchline = (shape factor / on-line AS spacing) x(Number of AS x area spacing of sprinklers) 0.5The shape factor is 1.2 for slope less than or equal to 5°.The shape factor is 1.4 for slope greater than 5° and up to 10°.Round these equations to the nearest whole number using standard rounding methods (i.e., rounddown if the resulting fraction is 0.49 or less, and round up if the resulting fraction is 0.50 or greater).System Types: For the wet-type sprinkler system designs outlined above, wet-pipe sprinkler systemsor pre-action sprinkler systems whose sprinkler protection design can be based on the equivalent ofa wet-pipe system are acceptable. For the dry-type sprinkler system designs outlined above, dry-pipesprinkler systems, pre-action sprinkler systems whose sprinkler protection design can be based onthe equivalent of a dry-pipe system or refrigerated area sprinkler systems are acceptable.SPRINKLER SPACINGCeiling Height(Up To and Including)30 ft/9.1mabove30 ft/9.1mand up to40 ft/12.3mMinimumLinearDistanceBetween<strong>Sprinkler</strong>sMaximumLinearDistanceBetween<strong>Sprinkler</strong>s8 ft/2.4m 12 ft/3.6mMinimum MaximumArea of Area ofCoverage Coverage80 ft 2 / 7.43m 2 100 ft 2 / 9.29m 2MinimumLinearDistanceBetween<strong>Sprinkler</strong>sMaximumLinearDistanceBetween<strong>Sprinkler</strong>s8 ft/2.4m 10 ft/3mMinimum MaximumArea of Area ofCoverage Coverage80 ft 2 / 7.43m 2 100 ft 2 / 9.29m 2<strong>Sprinkler</strong> Location from Walls: Locate the automatic sprinklers with respect to walls asfol<strong>low</strong>s (measured perpendicular to the wall):• Minimum horizontal distance: 4 in/100 mm• Maximum horizontal distance unless indicated otherwise in either the occupancy-specificoperating standard or the Approval Guide:(a) Wall angle greater than 90°: 5 ft/1.5 m(b) Wall angle equal to or less than 90°: 7 ft/2.1 m<strong>Sprinkler</strong> Location from Ceilings: Locate the centerline of the automatic sprinkler’s thermalsensing element with respect to the vertical distance be<strong>low</strong> ceilings as fol<strong>low</strong>s:• Minimum vertical distance: 2 in/50 mm for smooth ceilings or 4 in/100 mm for nonsmoothceilings• Maximum vertical distance: 12"/305 mmObstructions: For more information, reference FM Data sheet 2-0.www.victaulic.com<strong>Victaulic</strong> is a registered trademark of <strong>Victaulic</strong> Company. © 2013 <strong>Victaulic</strong> Company. All rights reserved.REV_G<strong>40.98</strong>_5


fire protection products – firelock automatic sprinklersFireLock ® LP-<strong>46</strong> Low Pressure <strong>Storage</strong> <strong>Sprinkler</strong>Model LP-<strong>46</strong> (SIN) V<strong>46</strong>03, K25.2, Standard Response <strong>Storage</strong> Upright <strong>Sprinkler</strong>MODEL LP-<strong>46</strong><strong>40.98</strong>dimensions Standard Upright – LP-<strong>46</strong> (SIN V<strong>46</strong>03)2 13/16[ 71mm ]3 9/16[ 91mm ]1 3/4[ 45mm ]available wrenches<strong>Sprinkler</strong> TypeOpen EndLP-<strong>46</strong> (SIN V<strong>46</strong>03) UprightV<strong>46</strong>www.victaulic.com<strong>Victaulic</strong> is a registered trademark of <strong>Victaulic</strong> Company. © 2013 <strong>Victaulic</strong> Company. All rights reserved.<strong>40.98</strong>_6REV_G


fire protection products – firelock automatic sprinklers<strong>40.98</strong>FireLock ® LP-<strong>46</strong> Low Pressure <strong>Storage</strong> <strong>Sprinkler</strong>Model LP-<strong>46</strong> (SIN) V<strong>46</strong>03, K25.2, Standard Response <strong>Storage</strong> Upright <strong>Sprinkler</strong>MODEL LP-<strong>46</strong>Nominal Wetting patterns Model LP-<strong>46</strong> (SIN V<strong>46</strong>03)Upright Spray Pattern1.02.0DISTANCE BELOW SPRINKLER FEET3.04.05.06.07.08.020 PSI or less40 PSI100 PSI or more9.010.0NOTES:1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0RADIAL DISTANCE FROM SPRINKLER FEET1 Data shown is approximate and can vary due to differences in installation.2 These graphs illustrate approximate wetting patterns for these specific <strong>Victaulic</strong> FireLockAutomatic <strong>Sprinkler</strong>s. They are provided as information for guidance and should not be usedas minimum sprinkler spacing rules for installation. <strong>Sprinkler</strong> location shall be in accordancewith FM Global Engineering Bulletin and/or Data Sheets. Failure to fol<strong>low</strong> these guidelinescould adversely affect the performance of the sprinkler and will void all Listings, Approvals andWarranties.3 All patterns are symmetrical to the waterway.www.victaulic.com<strong>Victaulic</strong> is a registered trademark of <strong>Victaulic</strong> Company. © 2013 <strong>Victaulic</strong> Company. All rights reserved.REV_G<strong>40.98</strong>_7


fire protection products – firelock automatic sprinklers<strong>40.98</strong>FireLock ® LP-<strong>46</strong> Low Pressure <strong>Storage</strong> <strong>Sprinkler</strong>Model LP-<strong>46</strong> (SIN) V<strong>46</strong>03, K25.2, Standard Response <strong>Storage</strong> Upright <strong>Sprinkler</strong>MODEL LP-<strong>46</strong>ordering informationPlease specify the fol<strong>low</strong>ing when ordering:<strong>Sprinkler</strong> Model NumberStyleTemperature RatingK-FactorThread SizeQuantity<strong>Sprinkler</strong> FinishEscutcheon FinishWrench Model Numberwarning WARNING• Always read and understand installation, care, and maintenanceinstructions, supplied with each box of sprinklers, before proceedingwith installation of any sprinklers.• Always wear safety glasses and foot protection.• Depressurize and drain the piping system before attempting toinstall, remove, or adjust any <strong>Victaulic</strong> piping products.• Installation rules, especially those governing obstruction, must bestrictly fol<strong>low</strong>ed.• Painting, plating, or any re-coating of sprinklers (other than that suppliedby <strong>Victaulic</strong>) is not al<strong>low</strong>ed.Failure to fol<strong>low</strong> these instructions could result in serious personalinjury and/or property damage.The owner is responsible for maintaining the fire protection system anddevices in proper operating condition. For minimum maintenance andinspection requirements, refer to the current National Fire ProtectionAssociation pamphlet that describes care and maintenance of sprinklersystems. In addition, the authority having jurisdiction may have additionalmaintenance, testing, and inspection requirements that must befol<strong>low</strong>ed.If you need additional copies of this publication, or if you have anyquestions about the safe installation of this product, contact <strong>Victaulic</strong>World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031USA, Telephone: 001-610-559-3300.warrantyRefer to the Warranty section of the current Price List or contact <strong>Victaulic</strong> for details.noteThis product shall be manufactured by <strong>Victaulic</strong> or to <strong>Victaulic</strong> specifications. All products to beinstalled in accordance with current <strong>Victaulic</strong> installation/assembly instructions. <strong>Victaulic</strong> reserves theright to change product specifications, designs and standard equipment without notice and withoutincurring obligations.For complete contact information, visit www.victaulic.com<strong>40.98</strong> 5563 REV G UPDATED 02/2013<strong>Victaulic</strong> is a registered trademark of <strong>Victaulic</strong> Company. © 2013 <strong>Victaulic</strong> Company. All rights reserved.<strong>40.98</strong>