7.6.8.5 The insulation of winding shall be designed to withstand voltage stress arising from surge intransmission lines due to atmospheric or transient conditions caused by switching etc.7.6.8.6 Tapping shall not be brought out from inside the coil or from intermediate turns and shall beso arranged as to preserve as far as possible magnetic balance of trans<strong>for</strong>mer at all voltageratios.7.6.8.7 Magnitude of impulse surges transferred from HV to LV windings by electro magneticinduction and capacitance coupling shall be limited to BILL of LV winding.7.6.8.8 The current density adopted in all winding shall not exceed 2.4 A/mm2. The total netcross sectional area of the strip conductors <strong>for</strong> calculating current density <strong>for</strong> eachwinding shall be obtained after deducting the copper area lost due to rounding up of thesharp edges at the rectangular conductors.7.7 INSULATING OIL7.7.1 The insulating oil <strong>for</strong> the trans<strong>for</strong>mer shall be of EHV grade, generally con<strong>for</strong>ming to IS: <strong>33</strong>5.No inhibitors shall be used in the oil.7.7.2 The quantity of oil required <strong>for</strong> the first filling of the trans<strong>for</strong>mer and its full <strong>specification</strong>shall be stated in the bid. The bidder shall quote the price of trans<strong>for</strong>mer <strong>com</strong>plete withall fittings, accessories and new trans<strong>for</strong>mer oil required <strong>for</strong> first filling plus 10% extraoil. The extra quantity of oil shall be supplied in non-returnable drums along with the oilrequired <strong>for</strong> the radiator banks.7.7.3 The design and materials used in the construction of the trans<strong>for</strong>mer shall be such as to reducethe risk of the development of acidity in the oil.7.7.4 The contractor shall warrant that oil furnished is in accordance with the following<strong>specification</strong>s.S.No Characteristic Requirement Method of Test01 Appearance The oil shall be clear &transparent & free fromsuspended matter or sediment02 Density at 20 0 C 0.89 g/cm 3 Max. IS:1448...... Kinematic Viscosity at 27 deg. 27 CST IS:1448C Max04 Interfacial tension at 27 0 C 0....... N/m IS:6104Min.05 Flash Point 136 0 C IS:144806 Pour Point Max. -6 0 C IS:144807 Nautralisation Value (Total 0....... mg KOH/gm IS:<strong>33</strong>5Acidity) Max.08 Electric strength Breakdown 72.5 KV IS:6792(voltage) Min.09 Dielectric dissipation factor tan 0....... Max IS:6262delta at 90 0 C10 Min specificresistance(resistively) at 90 0 C35X10 12 ohm cm (min.) IS:61......47A representative sample ofoil shall be examined in a100 mm thick layer atambient temp.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!