REX-D Series Initial Setting Manual - Cascade
REX-D Series Initial Setting Manual - Cascade
REX-D Series Initial Setting Manual - Cascade
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
(3) Alarm selection ( )ValueDescription<strong>Initial</strong> value priorto shipmentNo alarm functionWith alarm functionIn accordance withModel codeThis value is shown on the SV display unit,but do not set it. If it is set, malfunction mayresult.(4) Heater break alarm function type selection ( )CAUTIONSl If the heater break alarm function (for singlephase or threephase) is selected, always select" :With alarm" on " ".l If the continuous current/voltage output is selected, do not select the heater break alarm (for singlephaseor threephase).l If "Heater break alarm for threephase heater" is selected for <strong>REX</strong>D100, do not select the heating/cooling PID action with autotuning, contact input (STEP), analog output, or communicationfunction.l If "Heater break alarm function (for singlephase or threephase)" is selected for <strong>REX</strong>D700,no communication function RS422A can be used.Also, if "Heater break alarm for threephase heater" is selected do not select the heating/coolingPID action with autotuning, or analog output.l If "Heater break alarm for threephase heater" is selected for <strong>REX</strong>D400/D900, do not selectthe contact input (STEP).ValueDescriptionNo heater break alarm functionHeater break alarm for singlephase heaterHeater break alarm for threephase heater<strong>Initial</strong> value priorto shipmentIn accordance withModel code-6-