IEC 61 439-1 paragraph 11.4Protection against electric shocksand integrity of protection circuitsThe following should be checked visually:> Presence of protective shields againstdirect and indirect contacts on live parts;> Presence of the PE conductor.The continuity of protection circuits isensured by compliance with the assemblyinstructions delivered with each product.IEC 61 439-1 paragraph 11.5Integration of incorporatedcomponentsThe assembly manufacturer must complywith the instructions of the originalequipment manufacturer for installationand wiring of the components used.IEC 61 439-1 paragraph 11.6Internal electric circuitsand connections<strong>Schneider</strong> <strong>Electric</strong> recommends markingthe nut with a tinted acrylic lacquer, indelibleand temperature-resistant.This allows:> not only self-checking to check effectivetightening to torque;> but also identification of any loosening.IEC 61 439-1 paragraphe 11.9Dielectric propertiesThe main circuits, and the auxiliary andcontrol circuits connected to the main circuit,shall be subjected to the test voltage inaccordance.IEC 61 439-1 paragraph 11.10Wiring, operating performanceand functionVerification of wiring and marking conformitywith the drawings, parts list and diagram.Standard individualcheck sheetin accordance with the IEC 61439-1and 2 standard from the assemblymanufacturer (panelbuilder)Job No.: .................................................................................................Switchboard No.: ...................................................................................Drawing No./Rev. No.: ............................................................................Degrees of protection provided by enclosures 11.2Insulation clearances and creepage distances 11.3Protection against electric shocks and integrityof protection circuitsChapter11.4Integration of incorporated components 11.5Internal electric circuits and connections 11.6Terminals for external conductors 11.7Mechanical operation 11.8Dielectric properties 11.9Wiring, operating performance and function 11.10Date of verification:............ / ............ /.............Verifications performed by:Verified..........................................................................…………………………19

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!