PLUG “F” 10 WAYPIN DESCRIPTIONNo79 Generator L1 sensing input. Connect to alternator L1 output.80 Generator L2 sensing input. Connect to alternator L2 output. If using single phaseonly do not connect this terminal.81 Generator L3 sensing input. Connect to alternator L3 output. If using single phaseonly do not connect this terminal.82 Generator N sensing input. Connect to alternator N output.83 DO NOT USE84 DO NOT USE85 Mains L1 sensing input. Connect to mains L1 on live side of incoming mains supplycontactor.86 Mains L2 sensing input. Connect to mains L2 on live side of incoming mains supplycontactor. If using single phase only do not connect this terminal.87 Mains L3 sensing input. Connect to mains L3 on live side of incoming mains supplycontactor. If using single phase only do not connect this terminal.88 Mains N sensing input. Connect to mains N of incoming mains supply.28606 OPERATING MANUAL ISSUE 2 11/27/00 MR