SEQUENCE OF OPERATIONResidential and light duty commercial electric water heaters are designed to operate using several different operatingmodes. The common modes and sequence of operation are as follows:1. Single Element Operation.2. Double Element Non-Simultaneous Operation (single phase).3. Double Element Non-Simultaneous Operation (3 phase).4. Double Element Simultaneous Operation (single phase).5. Double Element Simultaneous Operation (3 phase).Sequence of Operation- Single Element Operation.1Line voltage is applied across terminalsL1 &L3 of the thermostat. ECO isclosed, so there is voltage at terminal L4and to one side of the element.1ECOClosed2Tank is cold therefore thermostatis closed at terminal T2 (calling for heat).This completes the circuit and allowscurrent to flow through the element.2Thermostat closedat terminal T23When the thermostat is satisfied, it opens atterminal T2 interrupting current flow through theelement. System is now in stand-by mode, waitingfor the next call for heat.Thermostat opensat terminal T23Page 66