TANK TEMPERATURE CONTROLLER - GW Kent
TANK TEMPERATURE CONTROLLER - GW Kent
TANK TEMPERATURE CONTROLLER - GW Kent
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
OFFstand—by, both outputs inactiveHEAheating control at output 1 onlyCOLCooling control at output 2 onlyH_Cheating control at output 1 and cooling control atoutput 2 -DiSDisplay of temperature only, both outputsdisabled4.2 Second ParametersThese parameters define the values of heating hysteresis, cooling hysteresis; and thedead zones.To set the Second Parameters- press and hold the [SET] button. When ‘PAS’ (password) is displayed- use the arrow keys to enter: [▲▼▲▼]- confirmed by pressing button [SET]. The display will then show the first parameter- select the desired parameter by pressing ▲▼- and confirm by pressing [SET] button- this will show the set value- to change the value press ▲▼- confirm by pressing [SET] button.Parameters are:Abv. Parameter Range Default DescriptionHSHHeatinghysteresis0.1...20after 0.11 heating hysteresis,temperature range within which theheating output does not change its