2.2 Certified System C<strong>on</strong>figurati<strong>on</strong>sFor safety-related operati<strong>on</strong> of the FSC Versi<strong>on</strong> 710.x, a c<strong>on</strong>figurati<strong>on</strong> in accordance with theSafety Integrity Level as per the following table shall be selected.Quad processor module 10020/1/1 and 10020/1/2 (dual processor):SystemSafety IntegrityLevelNumber of centralpartsMinimum numberof Bus Systems(Note 2, VBD10001/x/1)System resp<strong>on</strong>sein the event offaults, i.e. internalfault c<strong>on</strong>diti<strong>on</strong>sattributable to acentral part(Note 3)single CP -single I/O(DMR, 1oo2 voting)redundant CP -single I/O(QMR, 2oo4D voting)SIL 1 – 3 SIL 1 – 3 SIL 1 – 31 2 21 1System shutdownShutdown of defectivecentral part andc<strong>on</strong>tinued operati<strong>on</strong> forunlimited period usingintact central part(Note 1).redundant CP -redundant I/O(QMR, 2oo4D voting)2Shutdown of defectivecentral part andc<strong>on</strong>tinued operati<strong>on</strong> forunlimited period usingintact central part(Note 1).TÜV SÜD Rail GmbH 717506225Generic Safety Systems HH84623C_Rev1.0.docx / Rev. 1.0Barthstraße 16 • D-80339 Munich • GermanyAuthor: Martin BraunPh<strong>on</strong>e: +49 (89) 5190 -2899, Fax: -2933 05.02.2013E-Mail: martin.braun@tuev-sued.de Page 13 of 33