5.8 Fire Detecti<strong>on</strong> and Alarm Installati<strong>on</strong>s; N<strong>on</strong>-Product-Related C<strong>on</strong>diti<strong>on</strong>s5.8.1. The energy shall be provided by an un-interruptable power supply (UPS). The bridge-overdurati<strong>on</strong> and the alarm durati<strong>on</strong> will be determined by the applicati<strong>on</strong> and by the effectivenati<strong>on</strong>al requirements.5.8.2. The power supply of an alarm installati<strong>on</strong> following DIN VDE 0833 shall be independent ofthe supply of any other installati<strong>on</strong>.5.8.3. The installati<strong>on</strong> shall provide for an alarm horn of at least 60 dB and for a nuisance alarmof at least 50 dB.TÜV SÜD Rail GmbH 717506225Generic Safety Systems HH84623C_Rev1.0.docx / Rev. 1.0Barthstraße 16 • D-80339 Munich • GermanyAuthor: Martin BraunPh<strong>on</strong>e: +49 (89) 5190 -2899, Fax: -2933 05.02.2013E-Mail: martin.braun@tuev-sued.de Page 32 of 33