FIELD ASSEMBLY INSTRUCTIONS - BURNER1/8” end nozzle to end electrode Upper fins are open to allow light to cad cell7/16” center of nozzle to electrode 5/32” closest gap1) PRIOR TO INSTALLING BURNER, CHECK FOR SHIPPING DAMAGE TOFLAME RETENTION HEAD AND IGNITION ELECTRODE ALIGNMENT.2) If components are not as shown you can make adjustments to the electrodes by removingthe hole plug on top of burner tube near mount flange. With screw driver, loosen thescrew holding the electrode clamping plate. Adjust electrodes as shown. Re-tightenclamp screw. Do not over tighten or insulation on electrodes may crack. Examineelectrode position after tightening to be sure position has not changed. Replace holeplug.3) The electrodes should not touch surrounding metal parts or be within 3/16” as they willshort the arc and not light the oil spray.4) Attach burner to boiler. Grasp burner by the mount flange and motor, slip burner flangeover studs on hinged burner door and secure with nuts and washers.9