<strong>LP</strong>-<strong>Gas</strong> Regulators<br />
Indoor Installation of Regulators<br />
Regulators installed inside a building must have the bonnet vent<br />
piped away. To maintain the large vent capacity relief feature of<br />
the regulator, the vent piping should be at least as large as the vent<br />
opening on the regulator bonnet.<br />
To pipe away the LV4403B or LV5503B regulators, for example,<br />
remove the vent screen from the bonnet vent and install 3/4” pipe<br />
into the bonnet vent threads and pipe to the outside of building.<br />
Install vent protection on the outlet of the pipe away vent line.<br />
To utilize the vent screen and retainer supplied with the regulator,<br />
use a 3/4” NPT 90º elbow. Insert screen into 3/4” F.NPT outlet of<br />
elbow. Thread retainer into outlet at least 1 turn. Install the elbow<br />
with vent screen pointing down. The vent line must be installed in<br />
a manner to prevent the entry of water, insects, or foreign material<br />
that could cause blockage. The discharge opening must be at least<br />
3 feet from any opening below it.<br />
NOTE: Do not use regulators with over 5 PSIG inlet pressure<br />
indoors. Follow all local codes and standards as well as NFPA 54<br />
and 58.<br />
3/4” Elbow<br />
3/4” Elbow<br />
Vent Screen<br />
with supressor<br />
3/4” Pipe<br />
From 1 st stage<br />
regulator<br />
To appliances<br />
3/4” Elbow<br />
31