<strong>LP</strong>-<strong>Gas</strong> Regulators<br />

Indoor Installation of Regulators<br />

Regulators installed inside a building must have the bonnet vent<br />

piped away. To maintain the large vent capacity relief feature of<br />

the regulator, the vent piping should be at least as large as the vent<br />

opening on the regulator bonnet.<br />

To pipe away the LV4403B or LV5503B regulators, for example,<br />

remove the vent screen from the bonnet vent and install 3/4” pipe<br />

into the bonnet vent threads and pipe to the outside of building.<br />

Install vent protection on the outlet of the pipe away vent line.<br />

To utilize the vent screen and retainer supplied with the regulator,<br />

use a 3/4” NPT 90º elbow. Insert screen into 3/4” F.NPT outlet of<br />

elbow. Thread retainer into outlet at least 1 turn. Install the elbow<br />

with vent screen pointing down. The vent line must be installed in<br />

a manner to prevent the entry of water, insects, or foreign material<br />

that could cause blockage. The discharge opening must be at least<br />

3 feet from any opening below it.<br />

NOTE: Do not use regulators with over 5 PSIG inlet pressure<br />

indoors. Follow all local codes and standards as well as NFPA 54<br />

and 58.<br />

3/4” Elbow<br />

3/4” Elbow<br />

Vent Screen<br />

with supressor<br />

3/4” Pipe<br />

From 1 st stage<br />

regulator<br />

To appliances<br />

3/4” Elbow<br />

31