30.08.2015 Views

LP-Gas Serviceman’s Manual

LP-Gas Serviceman's Manual - cecogas

LP-Gas Serviceman's Manual - cecogas

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Leak Testing the Installation<br />

B. Gauge Adapter Method (High Pressure Testing Procedure)<br />

Step 1. Inspect all connections and appliance valves to be sure<br />

such connections are wrench tight and that all appliance valves are<br />

closed including the pilot valves.<br />

Step 2. Install 2962 high pressure test gauge adapter on the tank<br />

service valve and connect the other end of the gauge adapter to the<br />

pigtail and regulator inlet.<br />

Step 3. Open container valve to allow the system to pressurize<br />

while observing indicated pressure on 300 pound testing gauge.<br />

Step 4. Close service valve tightly. Note pressure reading on the<br />

pressure gauge, then slowly bleed gas between service valve and<br />

gauge adapter, reduce pressure to 10 PSIG less than the original<br />

reading on the gauge and retighten gauge adapter into service valve<br />

or close bleeder port. Note reading on gauge.<br />

If gauge reading remains constant for 3 minutes, it can be<br />

assumed the system is leak tight. If the pressure reading drops,<br />

it indicates a leak somewhere in the high or low pressure piping<br />

system. NOTE: A pressure drop of 15 psig in 10 minutes time<br />

indicates a leak as little as 10 BTU of gas per hour. Check joints<br />

and other possible points of leakage with an approved combustible<br />

gas detector, soap and water, or an equivalent nonflammable<br />

solution. CAUTION: Since some leak test solutions, including<br />

soap and water, may cause corrosion or stress cracking, the piping<br />

should be rinsed with water after testing, unless it is determined<br />

the leak test solution is noncorrosive. Never test with an open<br />

flame. If there is an increase in pressure it indicates the container<br />

valve is not shut off completely. Shut off container valve tightly<br />

and repeat step 4.<br />

Step 5. Disconnect the 2962 test gauge adapter from the service<br />

shut off valve. Reconnect pigtail, tighten and test with soap and<br />

water or an appropriate leak detector solution (refer to caution in<br />

step 4., above).<br />

Step 6. If required, proceed with manometer method steps 2<br />

through 4. Never check for leaks with an open flame.<br />

37

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!