06/05 Maintenance and Servicing<br />

11.5 Reforming the DC Link Capacitors<br />

Description<br />

If the cabinet unit is kept in storage for more than 2 years, the DC link capacitors<br />

have to be reformed. If this is not carried out, the cabinet may be damaged when<br />

the supply voltage is switched on.<br />

If the cabinet is commissioned within two years of its date of manufacture, the DC<br />

link capacitors do not need to be reformed. The date of manufacture is indicated in<br />

the serial number on the type plate (see "Device Overview").<br />

NOTE<br />

It is important that the period of storage is calculated as of the date of manufacture<br />

and not as of the delivery date.<br />

Procedure<br />

The DC link capacitors are reformed by applying the rated voltage without load for<br />

at least 30 minutes at room temperature.<br />

• Operation via PROFIBUS:<br />

– Set bit 3 of control word 1 (operation enable) permanently to "0".<br />

– Switch on the converter by means of an ON signal (bit 0 of the control word);<br />

all the other bits must be set in such a way that the converter can be<br />

operated.<br />

– Once the waiting time has elapsed, switch off the converter and restore the<br />

original PROFIBUS setting.<br />

• Operation via terminal block:<br />

– Set p0852 to "0" (factory setting is "1").<br />

– Switch on the converter (via digital input 0 on the customer terminal block).<br />

– Once the waiting time has elapsed, switch off the converter and restore the<br />

original setting for p0852.<br />

NOTE<br />

Reforming cannot be carried out in LOCAL mode via the AOP30.<br />