06/05 Electrical Installation<br />

6-pulse infeed -> open the disconnect switch<br />

For 6-pulse infeeds, disconnect switches –Q98 and –Q99 must be opened and it is<br />

not permissible that the DC links are connected with one another; this is the<br />

condition with the equipped is shipped.<br />

12-pulse infeed -> close the disconnect switches<br />

For 12-pulse infeeds, the disconnect switches –Q98 and –Q99 must be closed; the<br />

DC links must be connected with one another.<br />

4.7.3 Connecting the Motor and Power Cables<br />

Connecting the Motor and Power Cables on the Cabinet Unit<br />

NOTE<br />

The location of the connections is indicated in the layout diagrams provided in 3.<br />

1. Open the cabinet, remove the covers (if necessary) in front of the connection<br />

panel for motor cables (terminals U2/T1, V2/T2, W2/T3; X2) and power cables<br />

(terminals U1/L1, V1/L2, W1/L3; X1).<br />

2. Move or remove the bottom plate below the connection panel through which the<br />

motor cables are fed.<br />

3. Screw the protective earth (PE) into the appropriate terminal (with earth symbol)<br />

(50 Nm with M12) at the points provided in the cabinet.<br />

NOTE<br />

With version C, connect the power cables first and then the motor cables.<br />

4. Screw the motor cables onto the terminals.<br />

Make sure that you connect the conductors in the correct sequence: U2/T1,<br />

V2/T2, W2/T3 and U1/L1, V1/L2, W1/L3.<br />

CAUTION<br />

Tighten the screws with the appropriate torque (50 Nm with M12), otherwise the<br />

terminal contacts could catch fire during operation.<br />

NOTE<br />

The motor ground must be fed back directly to the cabinet unit and connected.<br />

SINAMICS G150<br />

Operating Instructions 4-15