BACnet® Protocol ACH550 AC Drives
ACH550 Bacnet Protocol User's Manual - HSL Automation
ACH550 Bacnet Protocol User's Manual - HSL Automation
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
16 <strong><strong>AC</strong>H550</strong> B<strong>AC</strong>net User’s Manual<br />
Diagnostics<br />
Fault Queue for Drive Diagnostics<br />
For general <strong><strong>AC</strong>H550</strong> diagnostics information, see “Diagnostics” in the <strong><strong>AC</strong>H550</strong><br />
User’s Manual. The three most recent <strong><strong>AC</strong>H550</strong> faults are reported to the fieldbus as<br />
defined below.<br />
Drive Parameter<br />
0401 Last Fault AV18<br />
0412 Previous Fault 1 AV19<br />
0413 Previous Fault 2 AV20<br />
B<strong>AC</strong>net Access Point<br />
Serial Communication Diagnostics<br />
Network problems can be caused by multiple sources. Some of these sources are:<br />
• Loose connections<br />
• Incorrect wiring (including swapped wires)<br />
• Incorrect baud rate<br />
• Bad grounding<br />
• Duplicate station numbers<br />
• Incorrect setup of drives or other devices on the network<br />
The major diagnostic features for fault tracing on an EFB network include Group 53<br />
EFB <strong>Protocol</strong> parameters 5306…5309. The “Parameter Descriptions” section, in the<br />
<strong><strong>AC</strong>H550</strong> User’s Manual, describes these parameters in detail.<br />
Diagnostic Situations<br />
The sub-sections below describe various diagnostic situations – the problem<br />
symptoms and corrective actions.<br />
Normal Operation<br />
During normal network operation, 5306…5309 parameter values act as follows at<br />
each drive:<br />
• 5306 EFB OK MESSAGES advances (advances for each application message<br />
properly received and addressed to this drive).<br />
• 5307 EFB CRC ERRORS does not advance at all (advances when an invalid<br />
message CRC is received).<br />
• 5308 EFB UART ERRORS does not advance at all (advances when character format<br />
errors are detected, such as parity or framing errors).<br />
• 5309 EFB status value varies depending on network traffic.<br />