16 <strong><strong>AC</strong>H550</strong> B<strong>AC</strong>net User’s Manual<br />

Diagnostics<br />

Fault Queue for Drive Diagnostics<br />

For general <strong><strong>AC</strong>H550</strong> diagnostics information, see “Diagnostics” in the <strong><strong>AC</strong>H550</strong><br />

User’s Manual. The three most recent <strong><strong>AC</strong>H550</strong> faults are reported to the fieldbus as<br />

defined below.<br />

Drive Parameter<br />

0401 Last Fault AV18<br />

0412 Previous Fault 1 AV19<br />

0413 Previous Fault 2 AV20<br />

B<strong>AC</strong>net Access Point<br />

Serial Communication Diagnostics<br />

Network problems can be caused by multiple sources. Some of these sources are:<br />

• Loose connections<br />

• Incorrect wiring (including swapped wires)<br />

• Incorrect baud rate<br />

• Bad grounding<br />

• Duplicate station numbers<br />

• Incorrect setup of drives or other devices on the network<br />

The major diagnostic features for fault tracing on an EFB network include Group 53<br />

EFB <strong>Protocol</strong> parameters 5306…5309. The “Parameter Descriptions” section, in the<br />

<strong><strong>AC</strong>H550</strong> User’s Manual, describes these parameters in detail.<br />

Diagnostic Situations<br />

The sub-sections below describe various diagnostic situations – the problem<br />

symptoms and corrective actions.<br />

Normal Operation<br />

During normal network operation, 5306…5309 parameter values act as follows at<br />

each drive:<br />

• 5306 EFB OK MESSAGES advances (advances for each application message<br />

properly received and addressed to this drive).<br />

• 5307 EFB CRC ERRORS does not advance at all (advances when an invalid<br />

message CRC is received).<br />

• 5308 EFB UART ERRORS does not advance at all (advances when character format<br />

errors are detected, such as parity or framing errors).<br />

• 5309 EFB status value varies depending on network traffic.<br />