01.10.2015 Views

BACnet® Protocol ACH550 AC Drives

ACH550 Bacnet Protocol User's Manual - HSL Automation

ACH550 Bacnet Protocol User's Manual - HSL Automation

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

20 <strong><strong>AC</strong>H550</strong> B<strong>AC</strong>net User’s Manual<br />

parameter 5314 to 1. When autobaud detection is enabled, drive parameter 5315<br />

displays the detected baud rate.<br />

Note! Autobaud detection samples for, and adjusts to, only the standard MS/TP<br />

baud rates (9600, 19200, 38400 & 76800).<br />

Max Info Frames Property<br />

Configure the Device Object Max Info Frames property using drive parameter 5312.<br />

Default: 5312 = 1.<br />

Max Master Property<br />

Configure the Device Object Max Master property using drive parameter 5313.<br />

Default: 5313 = 127.<br />

MS/TP Token Counter<br />

Parameter 5316 stores the count of MS/TP tokens passed to the associated node.<br />

Statement<br />

This statement is part of this Standard and is required for its use.<br />

B<strong>AC</strong>net <strong>Protocol</strong> Implementation Conformance Statement<br />

Date: June 1, 2005<br />

Vendor Name:<br />

Product Name:<br />

Product Model Number:<br />

ABB, Inc.<br />

Low Voltage <strong>AC</strong> Motor Drive<br />

<strong><strong>AC</strong>H550</strong><br />

Applications Software Version: 0503<br />

Firmware Revision:<br />

B<strong>AC</strong>net <strong>Protocol</strong> Revision: 2<br />

Product Description:<br />

B<strong>AC</strong>net Standardized Device Profile<br />

(Annex L):<br />

List all B<strong>AC</strong>net Interoperability Building<br />

Blocks Supported (Annex K):<br />

Segmentation Capability:<br />

206B<br />

The <strong><strong>AC</strong>H550</strong> is a high-performance adjustable frequency drive<br />

specifically designed for commercial automation applications. This<br />

product supports native B<strong>AC</strong>net, connecting directly to the MS/TP LAN.<br />

All standard MS/TP baud rates are supported, as well as master mode<br />

functionality. Over B<strong>AC</strong>net, the drive can be fully controlled as a standard<br />

adjustable frequency drive. In addition, up to 16 configurable I/O ports<br />

are available over B<strong>AC</strong>net for user applications.<br />

! B<strong>AC</strong>net Operator Workstation (B-OWS)<br />

! B<strong>AC</strong>net Building Controller (B-BC)<br />

! B<strong>AC</strong>net Advanced Application Controller (B-A<strong>AC</strong>)<br />

" B<strong>AC</strong>net Application Specific Controller (B-ASC)<br />

! B<strong>AC</strong>net Smart Sensor (B-SS)<br />

! B<strong>AC</strong>net Smart Actuator (B-SA)<br />

DS-RP-B, DS-WP-B, DM-DDB-B, DM-DOB-B, DM-DCC-B, DM-RD-B.<br />

! Segmented requests supported. Window Size ____<br />

! Segmented responses supported. Window Size ____<br />

Technical Data