BACnet® Protocol ACH550 AC Drives
ACH550 Bacnet Protocol User's Manual - HSL Automation
ACH550 Bacnet Protocol User's Manual - HSL Automation
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
26 <strong><strong>AC</strong>H550</strong> B<strong>AC</strong>net User’s Manual<br />
Instance<br />
ID<br />
BV19<br />
Object Name<br />
CTL OVERRIDE<br />
<strong>AC</strong>T<br />
Description<br />
This object indicates whether<br />
the drive is in B<strong>AC</strong>net Control<br />
Override. (See BV18.)<br />
BV20 START ENABLE 1 This object commands start<br />
enable1. Control requires<br />
parameter 1608 value =<br />
COMM.<br />
BV21 START ENABLE 2 This object commands start<br />
enable1. Control requires<br />
parameter 1609 value =<br />
COMM.<br />
Active/Inactive<br />
Text<br />
ON/OFF<br />
ENABLE/<br />
DISABLE<br />
ENABLE/<br />
DISABLE<br />
Present Value<br />
Access Type<br />
R<br />
C<br />
C<br />
Note! For Present Value Access Types, R = Read-only, W = Writeable,<br />
C = Commandable. Commandable values support priority arrays & relinquish<br />
defaults.<br />
Analog Input Object Instance Summary<br />
The following table summarizes the Analog Input Objects supported:<br />
Instance<br />
ID<br />
Object Name Description Units<br />
AI0 ANALOG INPUT 1 This object indicates the value of<br />
Analog Input 1. The corresponding<br />
drive parameter is 0120.<br />
AI1 ANALOG INPUT 2 This object indicates the value of<br />
Analog Input 2. The corresponding<br />
drive parameter is 0121.<br />
Percent<br />
Percent<br />
Present Value<br />
Access Type<br />
R<br />
R<br />
Note! For Present Value Access Types, R = Read-only, W = Writeable,<br />
C = Commandable. Commandable values support priority arrays & relinquish<br />
defaults.<br />
Technical Data