24.11.2015 Views

LED control gear Compact dimming Uconverter LCAI 15 W 350 mA one4all ECO series

TALEXXconverter LCAI 15 W one4all - Tridonic

TALEXXconverter LCAI 15 W one4all - Tridonic

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>LED</strong> <strong>control</strong> <strong>gear</strong><br />

<strong>Compact</strong> <strong>dimming</strong><br />

Expected life-time<br />

Type ta 40 °C 50 °C<br />

<strong>LCAI</strong> 0<strong>15</strong>/0<strong>350</strong> A020<br />

tc 70 °C 80 °C<br />

Life-time >100,000 h 50,000 h<br />

The <strong>LED</strong> <strong>control</strong> <strong>gear</strong> is designed for a life-time stated above under reference conditions and with a failure probability of less than 10 %.<br />

Maximum loading of automatic circuit breakers<br />

Automatic circuit breaker type C10 C13 C16 C20 B10 B13 B16 B20<br />

Installation Ø 1.5 mm 2 1.5 mm 2 1.5 mm 2 2.5 mm 2 1.5 mm 2 1.5 mm 2 1.5 mm 2 2.5 mm 2<br />

<strong>LCAI</strong> 0<strong>15</strong>/0<strong>350</strong> A020 60 80 100 125 60 80 100 125<br />

Wiring diagrams<br />

220–240 V AC , 0/50/60 Hz<br />

L<br />

N<br />

DALI/DSI<br />

~<br />

~<br />

DC + –<br />

<strong>Uconverter</strong><br />

<strong>LCAI</strong> ... Ax20<br />

DALI/DSI<br />

+<br />

–<br />

+<br />

–<br />

Umodule<br />

220–240 V AC, 0/50/60 Hz<br />

L<br />

N<br />

switchDIM<br />

~<br />

~<br />

DC + –<br />

<strong>Uconverter</strong><br />

<strong>LCAI</strong> ... Ax20<br />

+<br />

–<br />

+<br />

–<br />

Umodule<br />

Isolation and electric strength testing of luminaires<br />

Electronic devices can be damaged by high voltage. This has to be considered<br />

during the routine testing of the luminaires in production.<br />

According to IEC 60598-1 Annex Q (informative only!) or ENEC 303-Annex A, each<br />

luminaire should be submitted to an isolation test with 500 V DC for 1 second. This<br />

test voltage should be connected between the interconnected phase and neutral<br />

terminals and the earth terminal.<br />

The isolation resistance must be at least 2 MΩ.<br />

As an alternative, IEC 60598-1 Annex Q describes a test of the electrical strength<br />

with <strong>15</strong>00 V AC (or 1.414 x <strong>15</strong>00 V DC). To avoid damage to the electronic devices this<br />

test must not be conducted.<br />

Additional information<br />

Additional technical information at<br />

www.tridonic.com → Technical Data<br />

Guarantee conditions at<br />

www.tridonic.com → Services<br />

No warranty if device was opened.<br />

Data sheet 08/<strong>15</strong>-914-<strong>15</strong><br />

Subject to change without notice.<br />

www.tridonic.com 4

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!