Insulation Monitoring on Ungrounded Systems<br />
Ungrounded systems onboard ships <strong>and</strong> offshore platforms are continuously monitored<br />
by a BENDER ground detector. Connected between the active conductors <strong>and</strong><br />
ground (the hull), the detector superimposes a small measuring voltage onto the<br />
system. If a ground fault occurs, the measuring circuit is closed <strong>and</strong> a small measauring<br />
current will flow. The measuring current is proportional to the insulation resistance<br />
(the magnitude of the ground fault), <strong>and</strong> is evaluated by the detector.<br />
BENDER ground detectors employ the latest in detection technology, including the following:<br />
DC measuring voltage<br />
A frequently used measuring principle is<br />
the superimposition of a DC measuring<br />
voltage between the system <strong>and</strong> ground.<br />
This is the st<strong>and</strong>ard measuring principle for<br />
pure AC ungrounded systems, both single-<br />
<strong>and</strong> three-phase.<br />
Approvals<br />
Llyod’s Register<br />
of Shipping<br />
Underwriters<br />
Laboratories Inc.<br />
AMP measuring principle<br />
BENDER's AMP measuring principle overcomes<br />
the limitations of DC measuring<br />
signals by superimposing a clocked, pulsed<br />
measuring voltage onto the system. The<br />
signal is microprocessor controlled to<br />
automatically adapt itself to prevailing<br />
system conditions, such as high leakage<br />
capacitances. This signal is ideal for toda'ys<br />
modern power distribution systems that<br />
include: Pure DC systems, systems with a<br />
mix of AC <strong>and</strong> DC (including rectifiers), <strong>and</strong><br />
systems with variable frequency drives<br />
(VFDs).<br />
Type<br />
Fields of application<br />
Insulation monitoring<br />
Coupled systems / systems connected via tiebreaker<br />
Ungrounded systems with rectifiers / variable frequency drives<br />
Compatible with BENDER's ground fault location system<br />
System nominal voltage<br />
System frequency range<br />
Response values/contacts<br />
Number of response values<br />
Response values<br />
Contact, main alarm<br />
Contac, prewarning<br />
Contact, other<br />
Communication<br />
LCD display<br />
Pre-alarm display<br />
RS-485 interface<br />
Real time clock<br />
General features<br />
Measuring principle<br />
Capability to latch alarm<br />
Selective fault location L+/L-<br />
Connection monitoring<br />
Detailed history memory<br />
St<strong>and</strong>by capability<br />
<strong>Ground</strong> fault location<br />
Nominal voltage IRDH575B1-…<br />
Nominal voltage IRDH575B2-…<br />
Frequency range<br />
Evaluators<br />
Compatible current transformers<br />
Approvals
BENDER <strong>Ground</strong> Detectors for Ungrounded Systems<br />
Functions <strong>and</strong> characteristics at a glance<br />
IR1575 IRDH275B – IRDH375B IRDH575 IR420-D6<br />
Control <strong>and</strong> auxiliary circuits Main circuits Main circuits<br />
Control <strong>and</strong> auxiliary circuits<br />
Offline monitoring<br />
-- × × --<br />
-- × × --<br />
-- -- × --<br />
3(N)AC, DC, AC/DC 0 … 480 V 3(N)AC 0 … 793 V DC 0 … 650 V<br />
extentable via coupling unit<br />
see ”<strong>Ground</strong> fault location“ --<br />
DC, 30 … 460 Hz DC, 0.2 … 460 Hz DC, 42 … 460 Hz --<br />
2 2 2 2<br />
2 kΩ … 1 MΩ 1 kΩ … 10 MΩ 1 kΩ … 10 MΩ 100 kΩ…10 MΩ<br />
1 SPDT contact 1 SPDT contact 1 SPDT contact 1 SPDT contact<br />
1 SPDT contact 1 SPDT contact 1 SPDT contact 1 SPDT contact<br />
-- system fault system fault/EDS alarm --<br />
Two lines Two lines Four lines ×<br />
× × × --<br />
-- BMS protocol (B version) BMS protocol --<br />
-- × (B version) × --<br />
AMP AMPPlus AMPPlus DC<br />
× × × While in alarm<br />
× × × ×<br />
System <strong>and</strong> ground connections System <strong>and</strong> ground connections System <strong>and</strong> ground connections <strong>Ground</strong> connections<br />
-- × (B version) × --<br />
-- × (B version) × --<br />
-- -- AC, 3(N)AC 20 … 575 V DC 20 … 575 V --<br />
-- -- AC, 3(N)AC 340 … 760 V DC 340 … 575 V --<br />
-- -- DC, 42 … 460 Hz --<br />
-- -- EDS460/EDS461 --<br />
-- -- W, WS, WR series --<br />
-- GL, UL, LR LR, UL --<br />
3
4<br />
BENDER <strong>Ground</strong> Detectors - The Ideal Choice for Ungrounded<br />
Systems on <strong>Ships</strong> <strong>and</strong> <strong>Offshore</strong> <strong>Platforms</strong><br />
General features of IRDH275/375/575 <strong>and</strong> IR1575<br />
n The latest in measurement technology for AC <strong>and</strong> DC ungrounded systems<br />
n Simple to operate<br />
The user-friendly menu structure <strong>and</strong> large keys make the device simple to operate<br />
n Clear indication<br />
Backlit, easy-to-read LCD display<br />
n A wide range of alarm values<br />
Two programmable alarms provide warnings when the insulation resistance<br />
drops below pre-set values<br />
n Easy to install <strong>and</strong> to connect<br />
Both DIN-rail <strong>and</strong> panel mounted devices are available. Panel mounted versions<br />
utilize color-coded, plug-in terminals for installation.<br />
Special features of IRDH275B/375B/575<br />
n Monitoring ungrounded systems connected via tiebreaker<br />
Both automatic <strong>and</strong> manual control of devices to ensure proper operation on<br />
systems connected via tiebreakers<br />
n Informed at the press of a button<br />
Additional information such as system leakage capacitance, parameter values etc.<br />
are immediately available at the press of the info button<br />
n Compatiblity with BENDER's ground fault location system<br />
IRDH575 series detectors may be connected to BENDER's EDS series ground fault<br />
location system, providing notification of where a fault is located<br />
n History memory<br />
By pressing the INFO key, additional information <strong>and</strong> up to 99 alarm messages<br />
with time <strong>and</strong> date stamp immediately available<br />
n Remote communication capable<br />
Detectors are compatible with BENDER's communication system, providing<br />
Ethernet, Modbus/TCP, or Modbus/RTU communication to main stations
Application Examples - Ungrounded Monitoring<br />
Insulation monitoring of a electric propulsion system with IRDH375B<br />
Insulation monitoring of secondary distribution system with IR1575<br />
5
6<br />
Application Examples - Ungrounded Monitoring<br />
Insulation monitoring of primary distribution system with IRDH375 – Insulation monitoring of secondary distribution system with IR1575<br />
Interconnected ungrounded systems<br />
Many ungrounded systems onboard<br />
ships <strong>and</strong> platforms with have systems<br />
interconnected via a tiebreaker. Depending<br />
on the system's operation, this<br />
tieberaker may be open or closed.<br />
BENDER's ground detectors allow for<br />
either automatic or manual control of<br />
the detectors' operation to ensure that<br />
only one device is active on a circuit at<br />
one time.
Offline Monitoring<br />
A-ISOMETER® IR420-D6<br />
Offline monitoring with IR420-D6<br />
Offline monitoring with IR420-D6<br />
n Provides safe monitoring of electrical insulation integrity in<br />
cer tain installations<br />
n Monitors the insulation resistance of de-energised TN, TT<br />
<strong>and</strong> IT systems, e. g. fire extinguisher pumps, slide-valve<br />
drives, st<strong>and</strong>by generators, deck machinery in offshore<br />
platforms <strong>and</strong> marine environment<br />
n Gives early warning of insulation degradation, before motors<br />
(or generators) with deteriorated insulation are in immediate<br />
danger of failing on start up<br />
n Early warning for preventive maintenance to be scheduled<br />
when convenient<br />
n Eliminates failure <strong>and</strong> the need for an emergency replacement<br />
or rewind<br />
n Two separate response values<br />
100 kΩ…10 MΩ<br />
7
8<br />
<strong>Ground</strong> <strong>Fault</strong> Location for Ungrounded Systems<br />
BENDER‘s complete ground fault location<br />
system helps increase the reliability of<br />
your system, reduce costs, <strong>and</strong> create predictive<br />
maintenance by locating ground<br />
faults quickly <strong>and</strong> easily. The EDS series<br />
extends the capabilities of the IRDH575<br />
ground detector to not only know that<br />
there is a problem, but to find it as well.<br />
EDS series location modules assist in<br />
automating the process of finding faults<br />
by connecting to subfeeders or loads<br />
<strong>and</strong> providing notification when a fault<br />
has been located. Remote indicators also<br />
work in conjunction with this system to<br />
notify nurse <strong>and</strong> technical stations quickly<br />
when a problem has occured. Remote<br />
communication solutions allow personnel<br />
in main stations to know when a problem<br />
has occured in real-time.<br />
Advantages of ground fault location with the EDS series<br />
Improved economic<br />
efficiency<br />
n Time <strong>and</strong> costs for maintenance<br />
are re duced<br />
n Weak points in the installation<br />
are recognized<br />
Insulation fault location with communication via FTC470<br />
Optimized maintenance<br />
n <strong>Ground</strong> fault location<br />
without disconnecting<br />
the electrical installation<br />
n Selective fault location by<br />
fast <strong>and</strong> precise localization<br />
of the faulty subcircuit<br />
n Centralized indication<br />
<strong>and</strong> operation with LCD<br />
display<br />
n Reduced maintenance<br />
costs<br />
Increased operating<br />
reliability<br />
n Electrical installations<br />
are kept at a high level of<br />
availability<br />
n Interruptions to systems<br />
on a single fault condition<br />
are avoided<br />
n More comfort for passengers<br />
<strong>and</strong> crew<br />
Flexible <strong>and</strong> configurable<br />
solutions<br />
n Cost-effective construction<br />
with modular system<br />
components<br />
n Current transformers are<br />
available in different sizes<br />
<strong>and</strong> shapes (round, rectangular<br />
<strong>and</strong> split core)
Components of the <strong>Ground</strong> <strong>Fault</strong> Location System<br />
Type of supply system AC, DC, AC/DC (mixed systems) AC, DC, AC/DC (mixed systems)<br />
Applikation Main circuit Control circuit<br />
Function <strong>Ground</strong> fault detector <strong>and</strong> ground fault location controller<br />
Type IRDH575 IR1575 IRDH575<br />
Nominal system voltage Un (B1) 3AC/AC 20…575 V DC 20…575 V DC/AC/3 AC 20…480 V 3AC/AC 20…150 V/DC 20…150 V<br />
(Version IRDH575B1-4227, RDH575B1-4235)<br />
Nominal system voltage Un (B2) 3AC/AC 340…760 V DC 340…575 V -- --<br />
Supply voltage --<br />
IRDH575B1-435<br />
IRDH575B2-435<br />
IRDH575B1-4235<br />
IR1575PG1-435<br />
IRDH575B1-427<br />
IRDH575B1W-4227<br />
AC 88…264 V<br />
DC 77…286 V<br />
AC 88…264 V<br />
DC 77…286 V<br />
AC 340…460 V<br />
AC 88…264 V<br />
DC 77…286 V<br />
DC 19,2… 72 V -- DC 19,2… 72 V<br />
IR1575PG1-434 -- AC 16…72 V, DC 10,2…84 V --<br />
Test current 10/25/50 mA 10/25 mA 1/2,5 mA<br />
Response values 1 kΩ …. 10 MΩ 1 kΩ … 1 MΩ 1 kΩ …. 10 MΩ<br />
LC display 4 x 20 characters 2x16 characters 4 x 20 characters<br />
alarm relay 3 changeover contacts 2 changeover contacts 3 changeover contacts<br />
Interface/protocol RS-485 (BMS) -- RS-485 (BMS)<br />
Address range 1…30 -- 1…30<br />
<strong>Ground</strong> fault location module<br />
Type EDS460-D/DG… EDS490-D… EDS460-L… EDS490-L… EDS461-D… EDS491-D… EDS461-L… EDS491-L…<br />
Graphic LCD × × -- -- × × -- --<br />
7-segment / LED display -- -- × × -- -- × ×<br />
US: DC 16…94 V,<br />
AC 42…460 Hz 16…72 V<br />
US: AC / DC 70…276 V<br />
AC 42…460 Hz<br />
EDS460-D-1,<br />
EDS460-DG-*<br />
EDS460-D/DG-2,<br />
EDS460-DG-2*<br />
EDS490-D-1 EDS460-L-1 EDS490-L-1 EDS461-D-1 EDS491-D-1 EDS461-L-1 EDS491-L-1<br />
EDS490-D-2 EDS460-L-2 EDS490-L-2 EDS461-D-2 EDS491-D-2 EDS461-L-2 EDS491-L-2<br />
Scanning time < 10 s for up to 1080 measuring channels < 10 s for up to 1080 measuring channels<br />
Response value 2…10 mA 0,2…1 mA<br />
Residual current display 100 mA...10 A (EDS460DG 20mA-2 A) 10 mA … 1 A<br />
Parameterization function × × -- -- × × -- --<br />
Error codes display × × × × × × × ×<br />
Address range 1…90 1…90 1…90 1…90<br />
Internal clock (RTC) × × -- -- × × -- --<br />
History memory × × -- -- × × -- --<br />
Alarm relay “Common alarm” 2 x 1 changeover contact 2 x 1 changeover contact<br />
Alarm relay per channel -- 12 x 1 N/O contact -- 12 x 1 N/O contact -- 12 x 1 N/O contact -- 12 x 1 N/O contact<br />
* EDS460-DG-…particularly for localising insulation faults in DC IT systems with a number of branch circuits where high system leakage capacitances are involved<br />
9
10<br />
Monitoring <strong>Ground</strong>ed <strong>and</strong> HRG Circuits<br />
RCMS series devices are multi-channel ground fault location<br />
modules which can monitor up to 12 separate circuits /<br />
branches per device. Multiple devices may be interconnected<br />
to each other to increase this amount. RCMS devices are<br />
designed for use on grounded <strong>and</strong> high-resistance grounded<br />
systems. RCMS modules are also compatible with BENDER's<br />
communication system, to provide remote notification to<br />
technicians in the event of an alarm.<br />
Typical applications include any equipment that is solidly or<br />
resistance grounded. On ships, this may include entertainment<br />
areas, <strong>and</strong> cabins. On offshore platforms, this may include<br />
topside equipment, such as motors.<br />
Residual current monitoring with communication via FTC470<br />
RCMS460-D-2
Communication solutions<br />
BENDER‘s line of communication products allow for fast<br />
notification of personnel when a problem has occured. Critical<br />
systems monitored by BENDER equipment may be connected<br />
to a variety of remote indicators to notify personnel of the<br />
current status of the system. Communication gateways bring<br />
your electrical safety network into the 21st century by displaying<br />
system information via several st<strong>and</strong>ard protocols, such<br />
8<br />
TCP/IP/Ethernet<br />
BENDER RS-485 Bus<br />
Visualization – PC / Touch<br />
Web<br />
Browser<br />
TCP/IP<br />
Modbus/TCP<br />
Modbus/TCP<br />
Inosoft<br />
VisiWin<br />
OPC<br />
Server<br />
Wizcon<br />
Supervisor<br />
InduSoft<br />
Studio<br />
OPC Modbus/TCP SCADA / BMS<br />
Communication possibilities with BENDER systems <strong>and</strong> devices<br />
1 - BENDER devices<br />
2 - MK2430 Remote Indicating Station<br />
3 - BENDER communication bus<br />
4 - COM460IP Ethernet / Modbus/TCP communication gateway<br />
4 - FTC470XMB Modbus/RTU communication gateway<br />
5 - FTC470XDP Profibus/DP communication gateway<br />
7 - Ethernet network or Modbus/TCP network<br />
8 - Connected PC with web browser or visualization software<br />
9 - OPC server connectivity capabilities<br />
3<br />
9<br />
7<br />
1<br />
4<br />
Wonderware,<br />
WinCC, ...<br />
2<br />
as Ethernet, MODBUS, <strong>and</strong> PROFIBUS. The Ethernet gateway<br />
device additionally features an easy-to-use status page, accessible<br />
through a web browser. E-mail <strong>and</strong> SMS messaging when<br />
an alarm has occurred is also available. Utilizing this communication<br />
system allows for timely <strong>and</strong> cost-effective deployment<br />
of service personnel <strong>and</strong> can help avoid equipment damage or<br />
failure.<br />
10<br />
Ethernet<br />
Modbus/TCP<br />
COM460IP<br />
11 12 13<br />
Router<br />
Modbus/TCP<br />
Modbus RTU<br />
Profibus DP<br />
WiFi<br />
5 6<br />
FTC470 XMB<br />
10 - SCADA / BMS connectivity capabilities<br />
11 - COM460IP capability: E-mail notification<br />
13 - COM460IP capability:<br />
Web browser based navigation via the Internet<br />
13 - COM460IP capability:<br />
SMS notification<br />
XDP<br />
11
Solutions For Your Electrical Safety Needs<br />
With our complete portfolio of relay protection products<br />
For over 70 years, BENDER has been a leader in meeting elecrtical safety needs with our large portfolio of ground fault<br />
protection products. BENDER products enhance the safety of electrical systems <strong>and</strong> help to save money, reduce downtime,<br />
<strong>and</strong> give the peace of mind that your system is protected by the latest in electrical safety technology.<br />
n <strong>Ground</strong> <strong>Fault</strong> Monitors <strong>and</strong> GFCIs for grounded <strong>and</strong> high-resistance grounded systems<br />
n <strong>Ground</strong> <strong>Fault</strong> Detectors for ungrounded systems<br />
n Voltage, Current, <strong>and</strong> Frequency Relays<br />
n Remote Communication Solutions<br />
<strong>Ground</strong> <strong>Fault</strong> <strong>Protection</strong> for Ungrounded Systems<br />
n A-ISOMETER® <strong>Ground</strong> Detector Series<br />
n EDS <strong>Ground</strong> <strong>Fault</strong> Location Systems<br />
<strong>Ground</strong> <strong>Fault</strong> <strong>Protection</strong> for <strong>Ground</strong>ed Systems<br />
n RCM Series <strong>Ground</strong> <strong>Fault</strong> Monitors for Single-Phase <strong>and</strong><br />
Three-Phase AC Systems<br />
n RCMA Series <strong>Ground</strong> <strong>Fault</strong> Monitors for Single-Phase AC,<br />
Three-Phase AC, <strong>and</strong> DC Systems<br />
n RCMS Series Multi-Channel <strong>Ground</strong> <strong>Fault</strong> Monitors for<br />
Single-Phase AC, Three-Phase AC, <strong>and</strong> DC Systems<br />
n Lifeguard Series <strong>Ground</strong> <strong>Fault</strong> Circuit Interrupters for<br />
Single-Phase AC, Three-Phase AC, <strong>and</strong> DC Systems<br />
North American Headquarters • Coatesville, PA<br />
Toll-Free: 800.356.4266 • Fax: 610.383.7100<br />
T M<br />
General Purpose <strong>Protection</strong> Relays<br />
n Undervoltage <strong>and</strong> Overvoltage Relays for AC <strong>and</strong> DC<br />
Systems<br />
n Overfrequency <strong>and</strong> Underfrequency Relays<br />
n Overcurrent <strong>and</strong> Undercurrent Relays for AC <strong>and</strong> DC<br />
Systems<br />
Communication Solutions<br />
Visit www.bender.<strong>org</strong> for information, tools, <strong>and</strong> more:<br />
n Complete listings of products, documentation, datasheets, <strong>and</strong> technical information<br />
n Knowledgebase of technical information answering your ground fault questions<br />
n Product selection tools, including ground fault relays, currrent transformers, <strong>and</strong> more<br />
n Local representative information<br />
n St<strong>and</strong>ard Protocol Converters for Ethernet, MODBUS, <strong>and</strong><br />
PROFIBUS<br />
n Customizable Visualization Capabilities<br />
n Simple System Integration<br />
www.bender.<strong>org</strong> • E-mail: info@bender.<strong>org</strong><br />
Canada • Brampton, ON<br />
Toll-Free: 800-243-2438 • Fax: 905-799-3051<br />
Document NAE1111780 / 01.2012 / © <strong>Bender</strong> Inc. All Rights Reserved.