Example: Voltage Stability<br />
A B<br />
• Case 1: No reactive support at B<br />
Load<br />
• 198 MW can be transferred from A to B before the voltage at B<br />
drops below 0.95 p.u.<br />
• However, the voltage collapses if a line is tripped when power<br />
transfer is larger than 166 MW<br />
• The maximum power transfer from A to B is thus 166 MW<br />
© Daniel Kirschen & Leigh Tesfatsion 2011 34