Example: Voltage Control under Normal Conditions<br />

A B<br />

Load<br />

• Controlling the voltage at B using the generator at A?<br />

Power Transfer [MW] VB [p.u.] VA [p.u.] QA [MVAr]<br />

49.0 1.05 0.95 -68.3<br />

172.5 0.95 1.05 21.7<br />

Table 5.1<br />

• Local voltage control is much more effective<br />

• Severe market power issues in reactive support<br />

© Daniel Kirschen & Leigh Tesfatsion 2011 40