20.01.2017 Views

EN electrical test equipment

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Overview<br />

Model AM-500-EUR Hexagon 110 Hexagon 120 Hexagon 340 37 XR-A 38 XR-A<br />

Display Digits 3 1 / 2<br />

digit, 1999 digits 3¾ digit, 4000 digits 3¾ digit, 4000 digits ¾ digit, 5000 digits 4 digit, 9999 digits 4 digit, 9999 digits<br />

True-RMS measurement AC AC AC+DC<br />

Bar graph • • •<br />

Ranges<br />

Voltage AC 1 mV... 600 V 0.1 mV... 1000 V 0.1 mV... 1000 V 0.01 mV... 1000 V 0.1 mV... 750 V 0.1 mV... 750 V<br />

Basic Accuracy* (1.0% + 3D) (1.5% + 5D) (1.5% + 5D) (0.5% + 3D) (1.2% + 10D) (1.2% + 10D)<br />

Frequency 45...400 Hz 50...500 Hz 50...500 Hz 40 Hz...20 kHz 45 Hz...2 kHz 45 Hz...2 kHz<br />

Voltage DC 1 mV... 600 V 0.1 mV... 1000 V 0.1 mV... 1000 V 0.01 mV... 1000 V 0.1 mV... 1000 V 0.1 mV... 1000 V<br />

Basic Accuracy* (0.8% + 3D) (0.3% + 4D) (0.3% + 4D) (0.08% + 2D) (0.1% + 5D) (0.25% + 5D)<br />

Current AC 0.1 µA...10 A<br />

0.1 µA…10 A<br />

(20A for 30 s)<br />

0.1 µA…10 A<br />

(20A for 30 s)<br />

0.1 µA…10 A<br />

(20A for 30 s) 0.01 µA... 10 A 0.01 µA... 10 A<br />

Basic Accuracy* (1.5% + 3D) (1.5% + 4D) (1.5% + 4D) (0.6% + 3D) (1.5% + 10D) (1.5% + 20D)<br />

Frequency 45...400 Hz 50 Hz...500 Hz 50...500 Hz 40 Hz…1 kHz 45 Hz...1 kHz 45 Hz...1 kHz<br />

Current DC 0.1 µA...10 A<br />

0.1 µA…10 A<br />

(20A for 30 s)<br />

0.1 µA…10 A<br />

(20A for 30 s)<br />

0.1 µA…10 A<br />

(20A for 30 s) 0.01 µA... 10 A 0.01 µA... 10 A<br />

Basic Accuracy* (1.2% + 3D) (1.2% + 3D) (1.2% + 3D) (0.2% + 4D) (0.5% + 10D) (0.5% + 10D)<br />

Resistance 1Ω…20 MΩ 0.1Ω…40 MΩ 0.1Ω…40 MΩ 0.01Ω…50 MΩ 0.1Ω…40 MΩ 0.1Ω…40 MΩ<br />

Diode and continuity <strong>test</strong> • • • • • •<br />

Capacitance 0.01 nF…3000 µF 0.01 nF... 3000 µF 0.01 nF... 9999 µA 0.01 nF... 400.0 µF 0.01 nF... 400.0 µF<br />

Frequency 5 Hz…1 MHz 5 Hz…1 MHz 5 Hz…125 kHz 3.00Hz...10MHz 3.00Hz...10MHz<br />

Temperature -20…+300 °C -50…+1000 °C -20...+1300°C<br />

Range selection<br />

Automatic • • • •<br />

Manual • • • •<br />

Data Hold • • • •<br />

Min/max value memory Max Hold Max Hold • • •<br />

Peak Hold • • •<br />

Relative measurement • • • • •<br />

Data logger/interface - / RS-232 - / RS-232 - / RS-232<br />

Auto Power Off • • • • •<br />

Battery 1 x 9 V 2 x 1.5 V 2 x 1.5 V 1 x 9 V 1 x 9 V 1 x 9 V<br />

Measurement Category CAT III/600 V<br />

CAT III/600V,<br />

CAT II/1000 V<br />

CAT III/600 V,<br />

CAT II/1000 V<br />

CAT IV/600 V,<br />

CAT III/1000 V<br />

CAT III/600V, CAT II/1000V CAT III/600V, CAT II/1000V<br />

Features Battery <strong>test</strong>,<br />

1.5 V/9 V<br />

Acoustic warning signal for<br />

incorrect jack connection<br />

Acoustic warning signal for<br />

incorrect Jack connection<br />

incl. temperature probe<br />

RS-232 interface<br />

Illuminated display<br />

Calibration and adjustment<br />

without opening the device<br />

Software optionally available<br />

Inductance measurement<br />

Acoustic warning signal in<br />

case of incorrect jack connection<br />

logic <strong>test</strong><br />

Magnetic hanger<br />

(MagneGrip TM )<br />

Current loop measurement<br />

(4….20mA) Software<br />

optionally available<br />

Magnetic hanger<br />

(MagneGrip TM )<br />

* = Basic accuracy figures are with regard to the best level of accuracy of the relevant measurement function<br />

25

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!