SPECIALTY SENSORS<br />

250<br />

SPECIALTY SENSORS<br />

CARBON DIOXIDE SENSORS<br />

MODEL 4GS<br />

DIMENSIONS WIRING<br />

in<br />

(cm)<br />

1.12<br />

(0.62)<br />

5.12<br />

(13.01)<br />

MOUNTING<br />

5.12<br />

(13.01)<br />

3.84<br />

(9.75)<br />

2.5<br />

(6.35)<br />

3.84<br />

(9.75)<br />

4GS Sensor<br />

0.62<br />

(1.58)<br />

1.75<br />

(4.44)<br />

3.0<br />

(7.62)<br />

1.1<br />

(2.79)<br />

8<br />

(20.32)<br />

Duct Aspiration Box (optional)<br />

1.25<br />

(3.17)<br />

(I) (V)<br />

Current Voltage<br />

Output Select<br />

Jumper<br />

V M<br />

I R<br />

24 VAC/DC IN<br />

24 VAC/DC COMMON<br />

RELAY<br />

RELAY<br />

CO2 OUT<br />

CO2 COMMON<br />

- +<br />

Analog<br />

Output<br />

(R) (M)<br />

Run<br />

or<br />

Menu<br />

Mode Select<br />

Jumper<br />

Enter<br />

Select<br />

Note: CO 2 Common and 24 VAC/DC Common<br />

are connected internally.<br />

Display Models Only<br />

18-30 VAC or<br />

18-40 VDC (no polarity)<br />

Control Relay (optional)<br />

Contacts make on rise in CO 2<br />

The 4GS should be mounted in an area that is representative of the conditioned space to be monitored. Avoid drafty<br />

windows and doorways that might tend to dilute the atmosphere being controlled. Mounting height of 4-1/2' to 5' (1.2<br />

to 1.5m) is recommended but is not critical since carbon dioxide diffuses rapidly in air.<br />

The 4GS comes factory-configured for 4-20 mA analog output. If voltage output is required, moving the jumper on the<br />

back of the unit from I to V will change the output to 0-10 VDC. The voltage output may, in turn, be changed to 0-5<br />

VDC, the sensing range adjusted, and the (optional) relay setpoint changed by use of the programming keys on the<br />

back of the 4GS and its optional LCD display. Units with no display will require the CAL-B-KEY calibration keypad for<br />

adjustment. Refer to the programming manual supplied with the 4GS for configuration and calibration instructions.<br />

ORDERING INFORMATION<br />

MODEL DESCRIPTION<br />

4GS-22C-06 Sensor with analog output only<br />

4GS-22CD-06 Sensor with analog output and display<br />

4GS-22CR-06 Sensor with analog output and relay<br />

4GS-22CDR-06 Sensor with analog output, display, and relay<br />

ACCESSORIES<br />

4GS-DM-KIT Duct-mount kit for 4GS sensor (order sensor separately)<br />

4GS-PT-KIT Impact sampling tube kit for 4GS sensor (order sensor<br />

separately)<br />

CAL-B-KEY Calibration keypad with cable and connector for 4GS sensor<br />

RELATED PRODUCTS<br />

UCK-1 Universal calibration kit<br />

GAS-CO2-800 Calibration gas (800 ppm) 17L bottle