SPECIALTY SENSORS<br />

292<br />

SPECIALTY SENSORS<br />

UNIVERSAL CALIBRATION KIT<br />

MODEL UCK<br />

DESCRIPTION<br />

The Model UCK Universal Calibration Kit contains everything<br />

needed to flow calibration gas through any gas-sensing<br />

device in the <strong>Trane</strong> <strong>Catalog</strong>. Adapters are included for the following:<br />

WCO, KCO Series carbon monoxide sensors; CD-1,<br />

CD-A, GM, 711271, 2001V, 8000, and 4GS carbon dioxide<br />

sensors; OS-1 oxygen depletion sensors; RLD-5, RLD-134a,<br />

and 301IRF, HGM refrigerant sensors; and GMT Series toxic<br />

and combustible gas sensors. The supplied adapters and tubing<br />

will also fit the majority of other gas detectors on the market<br />

today. With the Model UCK’s pressure gauge and restrictor<br />

assortment, any gas flow rate from 50 mL/min to 1000 mL/min<br />

may be achieved without the need for an expensive flow meter.<br />

Flow tables and instructions are included.<br />

FEATURES<br />

• Six assorted sizes of color-coded polyurethane<br />

tubing<br />

• Assorted barbed couplings and reducing couplings<br />

• Regulator (1.0 L/min) for 17L (non-corrosive), 58L<br />

(corrosive) gas cylinders, or both<br />

• Restrictors, 0.005"and 0.007"<br />

DIMENSIONS / WEIGHT<br />

Dimensions 16.4"W x 8.6"D x 7.5"H<br />

(41.6 x 21.9 x 19.0 cm)<br />

MODEL DESCRIPTION<br />

UCK-1 Kit with Regulator for Noncorrosive<br />

Gases (N 2 , CO 2 , CH 4 , H 2 , O 2 , CO, and<br />

refrigerants)<br />

UCK-2 Kit with Regulator for Corrosive<br />

Gases (NO 2 , H 2 S, SO 2 , NH 3 )<br />

UCK-3 Kit with Both Regulators<br />

GAS-N2 Nitrogen (N 2 ), 17L<br />

GAS-CO2-2000 2000 ppm Carbon Dioxide (CO 2 )<br />

in Nitrogen (N 2 ), 17L<br />

GAS-CO2-1000 1000 ppm Carbon Dioxide (CO 2 )<br />

in Nitrogen (N 2 ), 17L<br />

GAS-CO2-800 800 ppm Carbon Dioxide (CO 2 )<br />

in Nitrogen (N 2 ), 17L<br />

GAS-CO-200 200 ppm Carbon Monoxide (CO)<br />

in Air, 17L<br />

GAS-CO-100 100 ppm Carbon Monoxide (CO)<br />

in Air, 17L<br />

GAS-CO-50 50 ppm Carbon Monoxide (CO)<br />

in Air, 17L<br />

ORDERING INFORMATION<br />

• Cup adapter for solid-state sensors<br />

(OS-1, WCO, RLD-5, RLD-134a, others)<br />

• Plug adapter for electrochemical sensors (GMT, others)<br />

• Tubing sized for insertion or barbed connectors<br />

(RLD-IR, 4GS, CD-1, others)<br />

• Rugged, high-density poly toolbox with accessory shelf<br />

and room for two gas cylinders of either size<br />

Weight<br />

UCK-1, UCK-2 4.3 lb (1.95 kg)<br />

UCK-3 5.0 lb (2.27 kg)<br />

Gas cylinders 1.6 lb (0.82 kg) each<br />

MODEL DESCRIPTION<br />

GAS-NO2-5 5 ppm Nitrogen Dioxide (NO 2 )<br />

in Air, 58L<br />

GAS-CH4-2.5 2.5% Methane (CH 4 ) in Air, 17L<br />

GAS-H2-2 2.0% Hydrogen (H 2 ) in Air, 17L<br />

GAS-H2S-25 25 ppm Hydrogen Sulfide<br />

(H 2 S) in Air, 58L<br />

GAS-SO2-5 5 ppm Sulfur Dioxide (SO 2 ) in Air, 58L<br />

GAS-O2-18 18% Oxygen (O 2 ) in Nitrogen<br />

(N 2 ), 17L<br />

GAS-NH3-50 50 ppm Ammonia (NH 3 ) in<br />

Nitrogen (N 2 ), 58L<br />

GAS-R123-100 100 ppm R-123 in Air, 17L<br />

GAS-R11-500 500 ppm R-11 in Air, 17L<br />

GAS-R12-500 500 ppm R-12 in Air, 17L<br />

GAS-R134A-500 500 ppm R-134a in Air, 17L<br />

GAS-R22-500 500 ppm R-22 in Air, 17L<br />

RELATED PRODUCTS<br />

CAL-B-KEY Calibration keypad for 4GS carbon dioxide sensors without display<br />

CD-CAL Calibration kit for CD-1W and CD-1D without display