Series 56-EX500<br />
How to Order<br />
Input manifold<br />
Input block<br />
Input Unit Specifications<br />
Connection block<br />
Communication connector<br />
Number of connection blocks<br />
Block supply voltage<br />
Block supply current<br />
Current consumption<br />
Short circuit<br />
protection<br />
Enclosure<br />
Weight (g) Note)<br />
136<br />
<strong>ATEX</strong> category 3<br />
EEX500 IB1<br />
Input unit specification<br />
Connector type<br />
E M8 connector<br />
T M12 connector<br />
M M8 and M12 mixed<br />
56 -<br />
1<br />
2<br />
3<br />
4<br />
5<br />
Note) Not including the DIN rail weight.<br />
6<br />
EX500 IE 1<br />
Block type<br />
M8 connector, PNP specification<br />
M8 connector, NPN specification<br />
M12 connector, PNP specification<br />
M12 connector, NPN specification<br />
8-point integrated type,<br />
M8 connector, PNP specifications<br />
8-point integrated type,<br />
M8 connector, NPN specifications<br />
Current source type input block (PNP input block)<br />
or<br />
Current sink type input block (NPN input block)<br />
M12 connector (8 pins, plug)<br />
Maximum 4 blocks<br />
24 VDC<br />
0.3 A maximum<br />
100 mA or less (at rated voltage)<br />
1A Typ. for each unit (shut off power supply)<br />
To restart, remove power to the GW unit once,<br />
then reapply it.<br />
IP65<br />
100 (Input unit + end block)<br />
1<br />
…<br />
4<br />
E 4<br />
Stations<br />
1 station<br />
…<br />
4 stations<br />
Example<br />
M8 and M12 on a single manifold<br />
Input block<br />
56-EX500-IE1 (2 sets)<br />
Unit side<br />
Input block<br />
56-EX500-IE3 (2 sets)<br />
56-EX500-IB1<br />
When ordering an input block manifold, enter the<br />
Input manifold part no. + Input block part no. together.<br />
The input block , end block and DIN rail are included<br />
in the input manifold. Refer to How to Order below.<br />
Input Block Specifications<br />
Applicable sensor<br />
Sensor connector<br />
Number of inputs<br />
Rated voltage<br />
Logical ''1''<br />
input voltage<br />
Logical ''0''<br />
input voltage<br />
Logical ''1''<br />
input current<br />
Logical ''0''<br />
allowable current<br />
Current source type<br />
(PNP output)<br />
EEX500-IB1-M4 1 set<br />
∗ 56-EX500-IE1 2 sets<br />
∗ 56-EX500-IE3<br />
End block side<br />
2 sets<br />
Current sink type<br />
(NPN output)<br />
M8 connector (3 pins) or, M12 connector (4 pins)<br />
2 inputs/8 inputs (M8 only)<br />
24 VDC<br />
15 V to 26.4 V<br />
0 V to 5 V<br />
5 mA Typ.<br />
1.5 mA<br />
0 V to 8 V<br />
19 V to 26.4 V<br />
–5 mA Typ.<br />
–1.5 mA<br />
Input delay<br />
1 m sec. or less<br />
Indicator<br />
Green LED<br />
Insulation<br />
Not provided<br />
Sensor supply current<br />
Maximum 30 mA/Sensor<br />
Ambient operating<br />
+5 to +45°C at 35% to 85% RH<br />
temperature/humidity<br />
(without condensation)<br />
Enclosure<br />
IP65<br />
Weight (g)<br />
[For M8: 20] [For M12: 40] [8 point integrated type, for M8: 55]