ATYS and SIRCOVER <strong>UL</strong> 1008 transfer switching equipment ensure:<br />

Maintenance free transfer switching equipment with a robust and<br />

reliable design.<br />

Power control and safety between a normal and an alternate source.<br />

Integrated and robust switch disconnection.<br />

A stable OFF position with integrated padlocking to facilitate safe<br />

downstream maintenance.<br />

Positive break indication with clear visible position indication I - 0 - II.<br />

An inherent failsafe mechanical interlock prevents asynchronous<br />

paralleling of the two sources.<br />

Stable positions (I – 0 – II) non-affected by typical vibration and<br />

shock.<br />

Constant pressure on the contacts non affected by network voltage<br />

perturbation.<br />

Quick, easy and extremely safe manual operation.<br />

Along with the above, the ATyS also includes:<br />

A simple and secure motorization remote controls interface.<br />

Integrated switch position auxiliary contacts.<br />

An active “product availability” status feedback.<br />

Compatibility with virtually any make of ATS, AMF and Genset<br />

controller provided with volt-free contacts.<br />

Power supply continuity for most electrically controlled total<br />

system optional standby power applications.<br />

SOCOMEC <strong>UL</strong> products<br />

The ATYS <strong>UL</strong> is a full load break transfer switch where the main<br />

switching components are from proven technology devices<br />

(SIRCOVER - Manual Transfer Switches) also fulfilling requirements<br />

in <strong>UL</strong> 98 and IEC 60947-3 standards. The transfer is done in open<br />

transition with a minimum supply interruption during transfer ensuring<br />

full compliance with <strong>UL</strong> 1008 and IEC 60947-6-1 international TSE<br />

standards.<br />

As a stand-alone product, the ATyS is a non-automatic power transfer<br />

switch (an electrically operated transfer switch that is not self-acting),<br />

generally used in applications where the load is non-emergency, does<br />

not require automatic transfer and where operating persons can be<br />

made available to initiate the transfer.<br />

The electrical control of the ATyS <strong>UL</strong> may be direct through pushbuttons<br />

and dry contacts fitted onto the enclosure door or through a<br />

dedicated local or remote ATS controller.<br />

Your preferred brand of ATS controller, genset / AMF controller or<br />

power / building management system, may easily be paired with the<br />

ATyS to provide a complete automatic transfer switch to suit your<br />

needs.<br />

ATyS have three stable positions (I-0-II) which can be selected<br />

remotely, via volt-free contacts, or directly, through use of the<br />

emergency operation handle; emergency operation requires no supply<br />

to be present. The OFF position provides disconnection of both<br />

supplies ensuring downstream isolation for safe maintenance.<br />

<strong>UL</strong> Applications<br />

ATyS <strong>UL</strong>1008 transfer switches are rated from 100 to 1200 A and designed for use in total system optional standby power applications for<br />

the safe transfer of a load supply between a normal and an alternate source.<br />

Optional standby systems are those systems installed to provide an alternate source of power for structures for which a power outage could<br />

cause discomfort or interruption or damage to products or processes.<br />