22.08.2017 Views

Socomec UL General Catalog

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

DIRIS A-20<br />

Multifunction power metering & monitoring device - PMD<br />

Multi-measurement<br />

Electrical characteristics<br />

Current measurement (TRMS)<br />

Via CT primary<br />

9 999 A<br />

Via CT secondary<br />

5 A<br />

Measurement range<br />

0 … 11 kA<br />

Input consumption<br />

0.6 VA<br />

Measurement updating period<br />

1 s<br />

Accuracy 0.2%<br />

Permanent overload<br />

6 A<br />

Intermittent overload<br />

10 I n over 1 sec<br />

Voltage measurements (TRMS)<br />

Direct measurement between phases 50 … 500 VAC<br />

Direct measurement between phase<br />

and neutral<br />

28 … 289 VAC<br />

Input consumption<br />

0.1 VA<br />

Measurement updating period<br />

1 s<br />

Accuracy 0.2%<br />

Power measurement<br />

Measurement updating period<br />

1 s<br />

Accuracy 0.5%<br />

Power factor measurement<br />

Measurement updating period<br />

1 s<br />

Accuracy 0.5%<br />

Frequency measurement<br />

Measurement range<br />

45 … 65 Hz<br />

Measurement updating period<br />

1 s<br />

Accuracy 0.1%<br />

Terminals<br />

Energy accuracy<br />

Active (according to IEC 62053-22) Class 0.5 S<br />

Reactive (in acc. with CEI 62053-23) Class 2<br />

Auxiliary power supply<br />

Alternative voltage<br />

110 … 400 VAC<br />

AC tolerance ± 10%<br />

DC voltage<br />

120 … 289 VDC<br />

DC tolerance ± 20%<br />

Frequency<br />

50 / 60 Hz<br />

Power consumption<br />

10 VA<br />

Pulse or alarm output<br />

Number 1<br />

Type<br />

100 VDC - 0.5 A - 10 VA<br />

Max. number of manoeuvres 10 8<br />

Inputs<br />

Number 3<br />

Power supply<br />

10 … 30 VDC<br />

Minimum width of signal<br />

10 ms<br />

Minimum length between 2 pulses 18 ms<br />

Type<br />

Optical couplers<br />

Communication<br />

Link<br />

RS485<br />

Type<br />

2 to 3 half duplex wires<br />

Protocol<br />

MODBUS ® in RTU mode<br />

MODBUS ® speed<br />

1400 … 38400 baud<br />

Operating conditions<br />

Operating temperature range - 10 … + 55 °C / +14 °F … +131 °F<br />

Storage temperature - 20 … + 70 °C / -4 °F … +158 °F<br />

Relative humidity 95%<br />

DIRIS_578_a_1_x_cat<br />

V1<br />

DIRIS A20<br />

V2<br />

V3<br />

VN<br />

A U X<br />

S1 S2 S1 S2 S1 S2<br />

I1 I2 I3<br />

S1 - S2 : current inputs.<br />

AUX : auxiliary power supply U s .<br />

V1, V2, V3 & VN : voltage inputs.<br />

Module communication<br />

Output or alarm module<br />

Module with 3 inputs, 1 output<br />

DIRIS_579_a_1_x_cat<br />

0V - +<br />

RS485<br />

Connection<br />

1<br />

0n<br />

R = 120<br />

DIRIS A20<br />

RS485 link.<br />

R = 120 : internal resistance for<br />

the RS485 link.<br />

Low voltage balanced network<br />

DIRIS_580_b_1_x_cat<br />

DIRIS A20<br />

18 19<br />

OUT 1<br />

18 - 19 : output n°1<br />

+ - + - + -<br />

12 13 14 15 16 17<br />

IN 3<br />

DIRIS A20<br />

Recommendation<br />

- For IT earthing systems, it is recommended that the CT secondary is not connected to earth.<br />

- When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out automatically<br />

by a SOCOMEC PTI: please consult us.<br />

3/4 wires with 1 CT Single-phase Two-phase<br />

N<br />

P1<br />

P1<br />

L1<br />

L1<br />

S1 S2<br />

S1 S2<br />

L2<br />

N<br />

L3<br />

IN 2<br />

IN 1<br />

P1<br />

S1<br />

19 18<br />

OUT 1<br />

S2<br />

L1<br />

L2<br />

1 1 1<br />

1<br />

1 1<br />

diris_392_d_1_x_cat<br />

V1 V2 V3 VN<br />

S1<br />

I1<br />

S2<br />

S1<br />

I2<br />

S2<br />

S1<br />

I3<br />

S2<br />

diris_393_d_1_x_cat<br />

V1 V2 V3 VN<br />

S1 S2 S1 S2 S1 S2<br />

I1 I2 I3<br />

diris_394_d_1_x_cat<br />

V1 V2 V3 VN<br />

S1 S2 S1 S2 S1 S2<br />

I1 I2 I3<br />

The 1CT solution reduces by 0.5% the accuracy of the phase<br />

for which the current is deduced by a vector calculation.<br />

1. 0.5 A gG / 0.5 A class CC fuses.<br />

1. 0.5 A gG / 0.5 A class CC fuses.<br />

1. 0.5 A gG / 0.5 A class CC fuses.<br />

264 <strong>General</strong> <strong>Catalog</strong> <strong>UL</strong>/CSA Ed. 2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!