DIRIS A-20<br />
Multifunction power metering & monitoring device - PMD<br />
Multi-measurement<br />
Electrical characteristics<br />
Current measurement (TRMS)<br />
Via CT primary<br />
9 999 A<br />
Via CT secondary<br />
5 A<br />
Measurement range<br />
0 … 11 kA<br />
Input consumption<br />
0.6 VA<br />
Measurement updating period<br />
1 s<br />
Accuracy 0.2%<br />
Permanent overload<br />
6 A<br />
Intermittent overload<br />
10 I n over 1 sec<br />
Voltage measurements (TRMS)<br />
Direct measurement between phases 50 … 500 VAC<br />
Direct measurement between phase<br />
and neutral<br />
28 … 289 VAC<br />
Input consumption<br />
0.1 VA<br />
Measurement updating period<br />
1 s<br />
Accuracy 0.2%<br />
Power measurement<br />
Measurement updating period<br />
1 s<br />
Accuracy 0.5%<br />
Power factor measurement<br />
Measurement updating period<br />
1 s<br />
Accuracy 0.5%<br />
Frequency measurement<br />
Measurement range<br />
45 … 65 Hz<br />
Measurement updating period<br />
1 s<br />
Accuracy 0.1%<br />
Terminals<br />
Energy accuracy<br />
Active (according to IEC 62053-22) Class 0.5 S<br />
Reactive (in acc. with CEI 62053-23) Class 2<br />
Auxiliary power supply<br />
Alternative voltage<br />
110 … 400 VAC<br />
AC tolerance ± 10%<br />
DC voltage<br />
120 … 289 VDC<br />
DC tolerance ± 20%<br />
Frequency<br />
50 / 60 Hz<br />
Power consumption<br />
10 VA<br />
Pulse or alarm output<br />
Number 1<br />
Type<br />
100 VDC - 0.5 A - 10 VA<br />
Max. number of manoeuvres 10 8<br />
Inputs<br />
Number 3<br />
Power supply<br />
10 … 30 VDC<br />
Minimum width of signal<br />
10 ms<br />
Minimum length between 2 pulses 18 ms<br />
Type<br />
Optical couplers<br />
Communication<br />
Link<br />
RS485<br />
Type<br />
2 to 3 half duplex wires<br />
Protocol<br />
MODBUS ® in RTU mode<br />
MODBUS ® speed<br />
1400 … 38400 baud<br />
Operating conditions<br />
Operating temperature range - 10 … + 55 °C / +14 °F … +131 °F<br />
Storage temperature - 20 … + 70 °C / -4 °F … +158 °F<br />
Relative humidity 95%<br />
DIRIS_578_a_1_x_cat<br />
V1<br />
DIRIS A20<br />
V2<br />
V3<br />
VN<br />
A U X<br />
S1 S2 S1 S2 S1 S2<br />
I1 I2 I3<br />
S1 - S2 : current inputs.<br />
AUX : auxiliary power supply U s .<br />
V1, V2, V3 & VN : voltage inputs.<br />
Module communication<br />
Output or alarm module<br />
Module with 3 inputs, 1 output<br />
DIRIS_579_a_1_x_cat<br />
0V - +<br />
RS485<br />
Connection<br />
1<br />
0n<br />
R = 120<br />
DIRIS A20<br />
RS485 link.<br />
R = 120 : internal resistance for<br />
the RS485 link.<br />
Low voltage balanced network<br />
DIRIS_580_b_1_x_cat<br />
DIRIS A20<br />
18 19<br />
OUT 1<br />
18 - 19 : output n°1<br />
+ - + - + -<br />
12 13 14 15 16 17<br />
IN 3<br />
DIRIS A20<br />
Recommendation<br />
- For IT earthing systems, it is recommended that the CT secondary is not connected to earth.<br />
- When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out automatically<br />
by a SOCOMEC PTI: please consult us.<br />
3/4 wires with 1 CT Single-phase Two-phase<br />
N<br />
P1<br />
P1<br />
L1<br />
L1<br />
S1 S2<br />
S1 S2<br />
L2<br />
N<br />
L3<br />
IN 2<br />
IN 1<br />
P1<br />
S1<br />
19 18<br />
OUT 1<br />
S2<br />
L1<br />
L2<br />
1 1 1<br />
1<br />
1 1<br />
diris_392_d_1_x_cat<br />
V1 V2 V3 VN<br />
S1<br />
I1<br />
S2<br />
S1<br />
I2<br />
S2<br />
S1<br />
I3<br />
S2<br />
diris_393_d_1_x_cat<br />
V1 V2 V3 VN<br />
S1 S2 S1 S2 S1 S2<br />
I1 I2 I3<br />
diris_394_d_1_x_cat<br />
V1 V2 V3 VN<br />
S1 S2 S1 S2 S1 S2<br />
I1 I2 I3<br />
The 1CT solution reduces by 0.5% the accuracy of the phase<br />
for which the current is deduced by a vector calculation.<br />
1. 0.5 A gG / 0.5 A class CC fuses.<br />
1. 0.5 A gG / 0.5 A class CC fuses.<br />
1. 0.5 A gG / 0.5 A class CC fuses.<br />
264 <strong>General</strong> <strong>Catalog</strong> <strong>UL</strong>/CSA Ed. 2