DIRIS A-30<br />

Multifunction power metering & monitoring device - PMD<br />

Connections<br />

Balanced low-voltage network for DIRIS A-30<br />

Recommendation: When disconnecting the DIRIS, the secondary of each current transformer must be short-circuited. This operation can be carried out<br />

automatically by a SOCOMEC PTI: please consult us. In TNC mode, it is advisable to connect the DIRIS A-30 to earth using the functional earth module.<br />

3/4 wires with 1 CTs<br />

P1<br />

S1<br />

S2<br />

N<br />

L1<br />

L2<br />

L3<br />

Single-phase<br />

P1<br />

S1<br />

S2<br />

L1<br />

N<br />

Two-phase<br />

P1<br />

S1<br />

S2<br />

L1<br />

L2<br />

diris_392_d_1_x_cat<br />

1 1 1<br />

V1 V2 V3 VN<br />

S1 S2<br />

I1<br />

S1 S2<br />

I2<br />

S1 S2<br />

I3<br />

diris_393_e_1_x_cat<br />

1<br />

V1 V2 V3 VN<br />

S1 S2 S1 S2 S1 S2<br />

I1<br />

I2<br />

I3<br />

diris_394_d_1_x_cat<br />

1 1<br />

V1 V2 V3 VN<br />

S1 S2 S1 S2 S1 S2<br />

I1<br />

I2<br />

I3<br />

The use of 1 CT reduces by 0.5% the accuracy of the phases,<br />

the current for which is worked out by vector calculation.<br />

1. 0.5 A gG / 0.5 A class CC fuses.<br />

1. 0.5 A gG / 0.5 A class CC fuses. 1. 0.5 A gG / 0.5 A class CC fuses.<br />

diris_395_d_1_x_cat<br />

Balanced low-voltage network for DIRIS A-30<br />

3/4 wires with 3 CTs<br />

3 wires with 2 CTs<br />

1 1 1<br />

V1 V2 V3 VN<br />

P1<br />

S1<br />

I1<br />

S2<br />

I2<br />

P1<br />

S1<br />

S1 S2 S1 S2 S1 S2<br />

I3<br />

N<br />

L1<br />

L2<br />

L3<br />

S2<br />

diris_396_d_1_x_cat<br />

1 1 1<br />

V1 V2 V3 VN<br />

P1<br />

S1<br />

I1<br />

S2<br />

I2<br />

P1<br />

S1<br />

S1 S2 S1 S2 S1 S2<br />

I3<br />

L1<br />

L2<br />

L3<br />

S2<br />

diris_397_d_1_x_cat<br />

3 wires with 2 CTs<br />

1 1 1<br />

V1 V2 V3 VN<br />

P1<br />

S1<br />

S1<br />

I1<br />

S2<br />

P1<br />

S1<br />

S1<br />

I2<br />

S2<br />

S2<br />

S1<br />

I3<br />

S2<br />

L1<br />

L2<br />

L3<br />

1. 0.5 A gG / 0.5 A class CC fuses. The use of 2 CTs reduces by 0.5% the accuracy of the<br />

phase, the current for which is worked out by vector calculation.<br />

1. 0.5 A gG / 0.5 A class CC fuses.<br />

The use of 2 CTs reduces by 0.5% the accuracy of the phase,<br />

the current for which is worked out by vector calculation.<br />

1. 0.5 A gG / 0.5 A class CC fuses.<br />

Additional information<br />

Communication via RS485 link<br />

Connection of potential transformer for HV<br />

networks<br />

L1<br />

L2<br />

L3<br />

AC and DC auxiliary power supply<br />

110 / 400 VAC<br />

120 / 350 VDC<br />

1<br />

1<br />

diris_398_c_1_x_cat<br />

0V - +<br />

RS485<br />

LIYCY-CY<br />

ON<br />

diris_399_b_1_x_cat<br />

V1 V2 V3 N<br />

diris_400_i_1_x_cat<br />

A U X<br />

1. 0.5 A gG / 0.5 A class CC fuses.<br />

260 <strong>General</strong> <strong>Catalog</strong> <strong>UL</strong>/CSA Ed. 2