<strong>UL</strong>/ CSA standards for disconnect switches<br />
<strong>UL</strong>98 - Enclosed and dead front switches<br />
(equivalent to CSA-C22.2 no 4)<br />
These requirements cover enclosed or dead front Switches,<br />
with or without provision for fuses, at 600 V or less.<br />
These products are used as disconnecting meanswithout<br />
restrictions ; they are heavy duty products requiring 2 inches<br />
(50 mm) minimum of creepage distance, which gives a<br />
maximum safety for users and installation. The short circuit<br />
withstand of those products goes up to 200 kA.<br />
Typical control panel<br />
<strong>UL</strong> 98 or <strong>UL</strong> 489<br />
Non fusible Disconnect switches<br />
SIRCO M <strong>UL</strong>98 and SIRCO <strong>UL</strong>98<br />
or<br />
Fusible Disconnect switches<br />
FUSERBLOC <strong>UL</strong><br />
sirco-ul_005_a_1_cat<br />
<strong>UL</strong>489 - Molded case switches<br />
(equivalent to CSA-C22.2 no 5)<br />
This requirements cover Molded-case Circuit Breaker, Molded<br />
case switches and fused Molded-case switches, rated at 600<br />
volts or less and 6 000 amperes or less.<br />
<strong>UL</strong> 508<br />
Non fusible switches<br />
SIRCO M <strong>UL</strong>508<br />
sircom_174_a<br />
<strong>UL</strong> standards for Electrical Machinery<br />
<strong>UL</strong>508 - Industrial Control Equipment<br />
(equivalent to CSA-C22.2 no 14)<br />
These requirements cover Manual, magnetic and solidstate<br />
Starters and Controllers, Overload relays, pushbuttons, selector<br />
switches, control lights…<br />
These products are IEC type products, smaller requiring only<br />
a creepage distance between phases of 1/2 inch. <strong>UL</strong>508<br />
standard requested only 5 kA or 10 kA as short circuit withstand<br />
with fuse protection. Their use as a disconnecting mean is<br />
therefore limited to local disconnection of motors. These<br />
products can only be used as a disconnect mean when they<br />
have been additionally tested “suitable as motor disconnect”.<br />
This additional testing ensures that the switch as a proper<br />
closing capacity on short circuit. <strong>UL</strong>508 (switches or Circuit<br />
breakers) can not be used as main disconnect of a electrical<br />
panel. (i.e. in entrance of control panels).<br />
NFPA 79 Electrical Standard for industrial machinery<br />
The following types of machines are identified as industrial<br />
machinery:<br />
metalworking machine tools, including machines<br />
that cut or form metal,<br />
plastics machinery,<br />
wood machinery, including woodworking, laminating, and<br />
sawmill machines,<br />
assembly machines,<br />
material handling machines, including industrial robots and<br />
transfer machines,<br />
inspection and testing machines, including coordinate<br />
measuring and in-process gauging machines.<br />
A manual motor controller marked “Suitable as motor<br />
disconnect” shall be installed only on the load side of<br />
the branch circuit protective device (<strong>UL</strong>508A 30.3.3 and<br />
NEC 430.109(6)).<br />
fuser_726_a<br />
fuser_727_a<br />