<strong>UL</strong>/ CSA standards for disconnect switches<br />

<strong>UL</strong>98 - Enclosed and dead front switches<br />

(equivalent to CSA-C22.2 no 4)<br />

These requirements cover enclosed or dead front Switches,<br />

with or without provision for fuses, at 600 V or less.<br />

These products are used as disconnecting meanswithout<br />

restrictions ; they are heavy duty products requiring 2 inches<br />

(50 mm) minimum of creepage distance, which gives a<br />

maximum safety for users and installation. The short circuit<br />

withstand of those products goes up to 200 kA.<br />

Typical control panel<br />

<strong>UL</strong> 98 or <strong>UL</strong> 489<br />

Non fusible Disconnect switches<br />

SIRCO M <strong>UL</strong>98 and SIRCO <strong>UL</strong>98<br />

or<br />

Fusible Disconnect switches<br />

FUSERBLOC <strong>UL</strong><br />

sirco-ul_005_a_1_cat<br />

<strong>UL</strong>489 - Molded case switches<br />

(equivalent to CSA-C22.2 no 5)<br />

This requirements cover Molded-case Circuit Breaker, Molded<br />

case switches and fused Molded-case switches, rated at 600<br />

volts or less and 6 000 amperes or less.<br />

<strong>UL</strong> 508<br />

Non fusible switches<br />

SIRCO M <strong>UL</strong>508<br />

sircom_174_a<br />

<strong>UL</strong> standards for Electrical Machinery<br />

<strong>UL</strong>508 - Industrial Control Equipment<br />

(equivalent to CSA-C22.2 no 14)<br />

These requirements cover Manual, magnetic and solidstate<br />

Starters and Controllers, Overload relays, pushbuttons, selector<br />

switches, control lights…<br />

These products are IEC type products, smaller requiring only<br />

a creepage distance between phases of 1/2 inch. <strong>UL</strong>508<br />

standard requested only 5 kA or 10 kA as short circuit withstand<br />

with fuse protection. Their use as a disconnecting mean is<br />

therefore limited to local disconnection of motors. These<br />

products can only be used as a disconnect mean when they<br />

have been additionally tested “suitable as motor disconnect”.<br />

This additional testing ensures that the switch as a proper<br />

closing capacity on short circuit. <strong>UL</strong>508 (switches or Circuit<br />

breakers) can not be used as main disconnect of a electrical<br />

panel. (i.e. in entrance of control panels).<br />

NFPA 79 Electrical Standard for industrial machinery<br />

The following types of machines are identified as industrial<br />

machinery:<br />

metalworking machine tools, including machines<br />

that cut or form metal,<br />

plastics machinery,<br />

wood machinery, including woodworking, laminating, and<br />

sawmill machines,<br />

assembly machines,<br />

material handling machines, including industrial robots and<br />

transfer machines,<br />

inspection and testing machines, including coordinate<br />

measuring and in-process gauging machines.<br />

A manual motor controller marked “Suitable as motor<br />

disconnect” shall be installed only on the load side of<br />

the branch circuit protective device (<strong>UL</strong>508A 30.3.3 and<br />

NEC 430.109(6)).<br />