Type Test Record for Digital Impulse Analyzers, Type MIA(S) - Highvolt
Type Test Record for Digital Impulse Analyzers, Type MIA(S) - Highvolt
Type Test Record for Digital Impulse Analyzers, Type MIA(S) - Highvolt
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Requirements time values<br />
U(T1,T2) ≤ 4.0 % <strong>for</strong> recorders of approved measuring<br />
systems<br />
U(T1,T2) ≤ 3.0 % <strong>for</strong> recorders of reference measuring<br />
systems<br />
Result<br />
U(T1,T2) ≤ 1.5 % by calibration certificate 2524 PTB 06<br />
U(T1,T2) ≤ 1.4 % by calibration certificate TKKSJ491<br />
Switching impulse calibration, expanded measuring uncertainty (1) of voltage and time values (SI)<br />
Requirements voltage values<br />
U(UP) ≤ 2.0 % <strong>for</strong> recorders of approved measuring systems<br />
U(UP) ≤ 0.7 % <strong>for</strong> recorders of reference measuring systems<br />
Result<br />
U(UP) ≤ 0.4 % by calibration certificate 2524 PTB 06<br />
U(UP) ≤ 0.2 % by calibration certificate TKKSJ491<br />
Requirements time values<br />
U(TP,T2) ≤ 4.0 % <strong>for</strong> recorders of approved measuring<br />
systems<br />
U(TP,T2) ≤ 3.0 % <strong>for</strong> recorders of reference measuring<br />
systems<br />
Result<br />
U(TP,T2) ≤ 1.5 % by calibration certificate 2524 PTB 06<br />
U(TP,T2) ≤ 1.0 % by calibration certificate TKKSJ491<br />
Front chopped lightning impulse calibration, expanded measuring uncertainty (1) of voltage and time values<br />
(LIC)<br />
Requirements voltage values<br />
U(UP) ≤ 3.0 % <strong>for</strong> recorders of approved measuring systems<br />
U(UP) ≤ 2.0 % <strong>for</strong> recorders of reference measuring systems<br />
Result<br />
U(UP) ≤ 0.6 % by calibration certificate 2524 PTB 06<br />
Requirements time values<br />
U(TC) ≤ 4.0 % <strong>for</strong> recorders of approved measuring<br />
systems<br />
U(TC) ≤ 3.0 % <strong>for</strong> recorders of reference measuring<br />
systems<br />
Result<br />
U(TC) ≤ 1.5 % by calibration certificate 2524 PTB 06<br />
© HIGHVOLT Prüftechnik Dresden GmbH - 0812 - 5-60-1-3.doc - Subject to change without prior notice<br />
δm(T)/%<br />
3,00<br />
2,00<br />
1,00<br />
0,00<br />
-1,00<br />
-2,00<br />
Time Deviation<br />
-3,00<br />
0,00 200,00 400,00 600,00 800,00 1000,00<br />
T1, positive polarity T1, negative polarity<br />
U / V<br />
T2, positive polarity T2, negative polarity<br />
δm(U)/%<br />
δm(U)/%<br />
δm(T)/%<br />
δm(T)/%<br />
1,00<br />
0,80<br />
0,60<br />
0,40<br />
0,20<br />
0,00<br />
-0,20<br />
-0,40<br />
-0,60<br />
-0,80<br />
-1,00<br />
Voltage Deviation<br />
0 100 200 300 400 500 600 700 800 900 1000<br />
Positive polarity<br />
Negative polarity<br />
U / V<br />
2,00<br />
1,50<br />
1,00<br />
0,50<br />
0,00<br />
-0,50<br />
-1,00<br />
-1,50<br />
-2,00<br />
1,50<br />
1,00<br />
0,50<br />
0,00<br />
-0,50<br />
-1,00<br />
-1,50<br />
4,00<br />
3,00<br />
2,00<br />
1,00<br />
0,00<br />
-1,00<br />
-2,00<br />
-3,00<br />
Time Deviation<br />
0 100 200 300 400 500 600 700 800 900 1000<br />
Tp, positive polarity Tp, negative polarity<br />
U / V<br />
T2, positive polarity T2, negative polarity<br />
Voltage Deviation<br />
0 100 200 300 400<br />
U / V<br />
500 600 700 800<br />
Positive polarity<br />
Negative polarity<br />
Time Deviation<br />
-4,00<br />
0 100 200 300 400 500 600 700 800<br />
TC, positive polarity<br />
TC, negative polarity<br />
U / V