Fiber Optic Cable Distances for 100 Mb/s Networks<br />

TIA/EIA 568 distance standards were initially written for a ‘FDDI (Fiber Distributed Data<br />

Interface) grade’ 62.5 µm multimode 160/500 MHz•km bandwidth fiber powered by 850<br />

µm Light Emitting Diodes (LEDs). These standards were written to support 100 Mb/s backbones<br />

with 10 Mb/s horizontal links. Using a fiber with higher bandwidth, or even using single-mode<br />

fibers, will produce longer transmission distances than defined by the standard.<br />

Outlet<br />

90 m<br />

Outlet<br />

300 meters in<br />

collapsed<br />

backbones<br />

Equipment room<br />

(intermediate<br />

crossconnect)<br />

In a 100 Mb/s network, the 90 meters of horizontal cabling can be either twisted pair or<br />

multimode fiber. Collapsed backbone connections should be multimode fiber and limited to<br />

300 meters. Campus links between active equipment should be limited to 2000 meters for<br />

multimode fiber.<br />

Single-mode fiber can be used anywhere in the network, but it is necessary where the<br />

transmission distance exceeds 2000 meters. Remember that single-mode fibers require the use<br />

of more expensive electronics.<br />

Fiber<br />

Description<br />

Bandwidth (MHz•km)<br />

850/1300 nm<br />

100 Mb/s Range<br />

with 850 nm LED<br />

50 µm OM4 4700*/500 300 m 2000 m<br />

50 µm OM3 2000*/500 300 m 2000 m<br />

50 µm OM2+ multimode 950*/500 300 m 2000 m<br />

50 µm OM2 multimode 500/500 300 m 2000 m<br />

62.5 µm multimode 200 /500 300 m 2000 m<br />

100 Mb/s Range<br />

with 1300 nm LED<br />

8.3 µm single-mode NA 2 km and up** 2 km and up**<br />

* Effective Modal Bandwidth (EMB)<br />

**using 1310 & 1550 nm lasers<br />

Telecommunications Room<br />

(horizontal crossconnect)<br />

2000 meters multimode<br />

3000+ meters single-mode<br />

300 meters between<br />

crossconnects<br />

total cabled distance between active<br />

(distributed<br />

equipment shall not exceed 2000<br />

backbones)<br />

meters for multimode fiber<br />

1700 meters multimode<br />

2500+ meters single-mode<br />

Central<br />

equipment<br />

room<br />

(main crossconnect)<br />

to Local<br />

Access<br />

www.commscope.com 27