Mountain Home Facility Plan Update 2019

Hydrant Test Calibration

Pressure Gauge Calibration @ Test 1B Location

Tank Diameters

Pressure Gauge A 65 psi 3 Tank 1 105 ft 2018 model MDD Original City MDD (2015)

Pressure Gauge B 67 psi 1 Tank 2 55 ft 8152.59 7747.31

Flow Gauge 69 psi -1 Tank 3 60 ft 2018 ADD Ratio of Total Flow to MDD

3000 0.26548

Ratio of Test 1 Flow (900 gpm)to 2018 MDD

Ratio of Test 1 System Demands to Total Flow

0.1103944 0.4228813

Note: Times are 1 hour ahead due to watch not being set back. So 11am is actually 10am, etc. Well 11 did not run other than during test 5

Tank Levels

Time of Residual

Test No. Reading

Flow Hydrant Pressure Hydrant A Pressure Hydrant B

Port 1 Pitot

Time of

Port 1 Pitot Flow Static

Static

Pressure

Time of

Residual

Residual

Pressure

Pressure Drop

(Static minus

Time of

Static

Static

Pressure

Time of

Residual

Residual

Pressure

Pressure (psi) (gpm) Reading (psi) Pressure (psi) Residual) (psi) Reading (psi) Pressure (psi)

Pressure Drop

(Static minus

Residual) (psi)

Static Level (ft)

Time of

Static

Reading Tank 1 Tank 2 Tank 3

Residual Level (ft)

Time of

Residual

Reading Tank 1 Tank 2 Tank 3

Time of

Static

Reading

Static Flow

(gpm)

Static

Pressure (psi)

Well 1 Well 11

Time of

Residual

Reading

Residual

Flow

(gpm)

Residual

Pressure

(psi)

Time of

Static

Reading

Static

Flow

(gpm)

Static

Pressure

(psi)

1 11:24:59 50 1187 11:13:00 65 11:25:25 54 11 11:14:24 66 11:26:10 54 12 11:19:38 26.5 22.3 26.2 11:28:30 26.3 22.1 26.4 11:16:26 672 57.8 11:27:46 672 56.5

2 12:06:00 40 1062 11:56:45 64 12:04:11 62 2 11:57:30 67 12:02:55 59 8 11:59:00 26.1 21.5 27.1 12:06:04 26 21.3 27.3 11:58:25 699 57.7 12:05:32 693 56.6

3 12:34:00 30 919 12:29:57 59 12:34:00 58 1 12:30:30 61 12:34:30 59 2 12:31:06 25.8 20.8 27.9 12:35:27 25.7 20.8 28 12:30:40 691 58.1 12:35:00 695 56.7

4 1:06:00 50 1187 1:01:40 58 1:06:30 55 3 1:02:10 60 1:07:00 56 4 1:02:52 25.5 21.2 27.9 1:08:55 25.4 21.2 27.9 1:02:22 691 56.8 1:07:11 699 55.8 1:06:20 0 56.3

5 1:30:00 45 1126 1:25:30 56 1:30:35 52 4 1:26:00 57 1:31:05 55 2 1:27:05 26.1 21.7 27.8 1:32:47 26.3 21.8 27.8 1:25:47 683 64.6 1:31:23 687 63.2 1:26:24 2040 80.2 1:31:40 2073 78.2

6 3:55:12 60 1300 3:49:00 75 3:55:50 62 13 3:49:45 82 3:56:20 67 15 3:52:11 27.9 23 27 3:59:13 27.8 23 26.9 3:50:00 700 58.6 3:56:30 703 58.2

7 3:14:36 92 1600 3:10:45 112 3:16:30 100 12 3:29:32 113 3:17:00 101 12 3:07:32 27.9 22.9 27.6 3:18:44 27.9 23 27.1 3:05:18 687 57.2 3:17:17 685 58.3

Test No.

Time of

Static

Reading

Well 13 did not run other than during test 5 Neither pilot pump ran during testing, effectively the same Pilot pump 3 did not run during testing 3rd street booster was turning off and on during testing

Only reported values where the demand may cause booster to kick on

Well 13

Pilot Pump 1 / Pilot Pump 2 Pilot Pump 3

3rd Street Booster

Static Static Time of

Residual Time of Static Static

Residual Residual Time of

Static Time of Residual Residual Time of

Time of Residual

Flow Pressure Residual Residual Flow Pressure Static Flow Pressure Time of Residual Flow Pressure Static Static Flow Pressure Residual Flow Pressure Static Static Flow Static Residual Flow

(gpm) (psi) Reading (gpm) (psi) Reading (gpm) (psi) Reading (gpm) (psi) Reading (gpm) (psi) Reading (gpm) (psi) Reading (gpm) Pressure (psi) Reading (gpm)

1

2

3

4 1:06:00 0 49.3

5 1:26:46 1887 74.6 1:32:10 1890 73

6 3:50:40 0 84.8 3:58:44 0 84.8 3:50:50 0 50.2 3:58:56 0 50.2 3:51:23 90 85 3:59:00 1,223 82.6

7 3:06:24 0 84.9 3:17:40 0 84.9 3:10:30 0 50.5 3:18:10 0 49.4 3:09:23 104 85.3 3:18:22 174 84.4

Pressure Hydrant A

Pressure Hydrant B

Time of Static Time of Residual Pressure Drop Time of Static Time of Residual Pressure Drop

Change In Change in

Change in

Change in

Change in Tank Flow

Test No

Updating

pressure

Static

Reading

Pressure

(psi)

Residual

Pressure

Pressure

(psi)

(Static minus

Residual) (psi)

Static

Reading

Pressure

(psi)

Residual

Pressure

Pressure

(psi)

(Static minus

Residual) (psi) Test

Time

(minutes)

Tank 1

level (ft) (ft^3)

Tank 2

level (ft) (ft^3)

Tank 3

level (ft) (ft^3) (ft^3)

volume all

tanks (gal)

into system

(gpm)

Well Flow

(gpm) (gpm)

Hydrant

Flow

System

Demands

1 hydrants to 11:13:00 69 11:25:25 58 11 11:14:24 68 11:26:10 56 12 1 8.9 (0.2) (1,731.8) (0.2) (475.2) 0.2 565.5 (1,641.5) (12,278.3) 1,384.8 672.0 2,056.8 1,187.0 869.8

2 match Flow 11:56:45 68 12:04:11 66 2 11:57:30 69 12:02:55 61 8 Static 30.5 (0.2) (1,731.8) (0.6) (1,425.5) 0.7 1,979.2 (1,178.1) (8,812.2) 288.9 685.5 974.4 - 974.4 "--> Run with 900 gpm for static condition"

3 Hydrant 12:29:57 63 12:34:00 62 1 12:30:30 63 12:34:30 61 2 2 7.1 (0.1) (865.9) (0.2) (475.2) 0.2 565.5 (775.6) (5,801.3) 820.9 696.0 1,516.9 1,062.0 454.9

4 1:01:40 62 1:06:30 59 3 1:02:10 62 1:07:00 58 4 4 6.1 (0.1) (865.9) - - - - (865.9) (6,476.9) 1,070.6 695.0 1,765.6 1187 578.6

5 1:25:30 60 1:30:35 56 4 1:26:00 59 1:31:05 57 2

6 3:49:00 79 3:55:50 66 13 3:49:45 84 3:56:20 69 15

7 3:10:45 116 3:16:30 104 12 3:29:32 115 3:17:00 103 12

Change in

Volume

tank 1

Analysis

Change in

Volume

tank 2

Change in

Volume

tank 3

Change

volume in

all Tanks

Total Flow

into

system

(Demand)

Residual

Pressure

(psi)

Time of

Residual

Reading

3285.98

696.98 ft

Residual

Flow

(gpm)

Residual

Pressure

(psi)

P:\214010 - Mountain Home\020 2018 WMP Update\b_Plan\PLAN CRITERIA\Fire Hydrant Flow Test Worksheets.xlsx