CAUTION! FOLLOW DIRECTIONS BEFORE APPLYING POWER<br />

POWER SUPPLY L1 AND L2 AT UNIT CONTACTOR MUST BE IN-PHASE WITH POWER SUPPLY L1 AND L2 AT ELECTRIC HEAT KIT OR DIRECT SHORT<br />

WILL OCCUR. THESE DIRECTIONS ARE FOR UNITS WITH ELECTRIC HEAT KITS SUPPLIED WITHOUT CIRCUIT BREAKER(S). SEE REVERSE FOR<br />

ELECTRIC HEAT KITS WITH CIRCUIT BREAKERS.<br />

WARNING<br />

HIGH VOLTAGE!<br />

Disconnect ALL power before servicing. Multiple power sources may be present.<br />

Failure to do so may cause property damage, personal injury or death.<br />

Technical <strong>Service</strong>s Department • 1810 Wilson Parkway • Fayetteville, TN 37334<br />

Main: 888.593.9988 • <strong>Service</strong> Fax: 931.438.2273<br />

®<br />

Is a trademark of Maytag Corporation and is used under license to Goodman Company, L.P.<br />

All rights reserved.<br />

SP-004<br />

1. TURN OFF POWER SUPPLY BREAKER AT HOUSE.<br />

2. AT HEAT KIT POWER TERMINAL BLOCK, NOTE POSITION OF RED WIRE THAT CONNECTS TO PLUG PIN #2 (PLUG IS SHOWN IN PHOTO ON<br />

REVERSE SIDE.) THE RED WIRE CONNECTS TO L2 AT THE TERMINAL STRIP.<br />

3. REMOVE RED WIRE FROM TERMINAL STRIP AND TAPE END TO INSULATE AND PREVENT SHOCK AND/OR SHORT<br />

4. CONNECT POWER TO L1 AND L2 AT UNIT CONTACTOR AND HEAT KIT POWER TERMINAL BLOCK. (SEPARATE OVER-CURRENT PROTECTION<br />

MUST BE SUPPLIED FOR EACH POWER SOURCE.)<br />

5. TURN ON POWER SUPPLY BREAKER AT HOUSE.<br />

6. USING A VOLT METER, CHECK FOR VOLTAGE BETWEEN L2 AT THE UNIT CONTACTOR AND L2 AT THE HEAT KIT POWER TERMINAL BLOCK.<br />

(SEE CONTROL BOX PHOTO ON REVERSE SIDE FOR CONTACTOR LEAD ORIENTATION.)<br />

7. IF THE POWER SUPPLIES ARE IN-PHASE, THERE WILL BE NO VOLTAGE BETWEEN UNIT CONTACTOR L2 AND HEAT KIT POWER TERMINAL<br />

BLOCK L2.<br />

8. IF THERE IS NO VOLTAGE, THEN THE POWER SUPPLIES ARE IN-PHASE AND THE UNIT IS WIRED CORRECTLY. SKIP TO STEP 12.<br />

9. IF THE POWER SUPPLIES ARE NOT IN-PHASE, THERE WILL BE LINE VOLTAGE READ BETWEEN L2 AT UNIT CONTACTOR AND L2 AT HEAT KIT<br />

POWER TERMINAL BLOCK.<br />

10. IF A VOLTAGE IS PRESENT, TURN OFF POWER AT HOUSE BREAKER.<br />

11. SWAP LINES L1 AND L2 AT UNIT CONTACTOR.<br />

12. REPEAT STEPS 4-7 ABOVE. VOLTAGE SHOULD BE ZERO.<br />

13. AFTER VERIFYING THAT THERE IS NO VOLTAGE BETWEEN L2 AT UNIT CONTACTOR AND L2 AT HEAT KIT POWER TERMINAL BLOCK WITH<br />

SOURCE POWER ON, TURN OFF POWER AT HOUSE AGAIN, AND RE-CONNECT RED WIRE TO HEAT KIT POWER TERMINAL BLOCK AT L2.<br />

14. TURN POWER BACK ON. UNIT IS NOW WIRED CORRECTLY.<br />

15. IF POWER SUPPLIES ARE NOT IN-PHASE, A DIRECT SHORT WILL OCCUR AND BREAKER(S) WILL TRIP. IF THIS OCCURS, TURN OFF MAIN<br />

POWER AND CHECK FOR DAMAGE TO ELECTRICAL COMPONENTS AND WIRES. IF NONE IS FOUND, REPEAT STEPS ABOVE TO CHECK POWER<br />

SUPPLY PHASING.<br />

Page 3 of 3