System overview<br />

Table 1:<br />

Maximum<br />

System expansion<br />

<strong>PROFIBUS</strong>-<strong>DP</strong><br />

Single-Master systems<br />

With mono-master systems merely a single master on the bus is active during bus operation.<br />

The PLC is the central control component. The slaves are coupled decentrally to the PLC via<br />

the transmission medium. With this type of system configuration the shortest bus cycle times<br />

are achieved.<br />

Multi-Master systems<br />

In multi-master operation there are several masters on the bus. These form independent subsystems,<br />

consisting of one <strong>DP</strong>M1 each and the associated slaves, or additional configuration<br />

and diagnostic devices. The slave input and output data can be read by all <strong>DP</strong> masters.<br />

Writing of outputs is reserved to a single <strong>DP</strong> master (the assigned <strong>DP</strong>M1 during configuration).<br />

Multi-Master systems achieve an average bus cycle time. In time-critical applications you<br />

should monitor the bus cycle time via a connected diagnostic tool.<br />

Topology<br />

<strong>PROFIBUS</strong>-<strong>DP</strong> communicates via a shielded 2-wire cable according to the RS485 standard.<br />

The network topology accords to a line structure with active bus terminators on both ends.<br />

Maximum system extension<br />

<strong>PROFIBUS</strong>-<strong>DP</strong> is suited for connection of a large number of I/O points. Up to 126 addressable<br />

bus nodes enable connection of thousands of analogue and digital I/O points within a<br />

network.<br />

<strong>PROFIBUS</strong>-<strong>DP</strong> allows a maximum of 32 nodes per segment; please note that masters and<br />

repeaters always count as nodes. One segment is defined as the bus section between two<br />

repeaters. If no repeaters are used, the entire network corresponds to one segment.<br />

Segments must comply with the specified maximum length and the specified transmission<br />

rates. Up to nine repeaters, type "REP-<strong>DP</strong>0002" may be connected within a network. The<br />

maximum length of a bus line within a segment and the number of repeaters are listed in the<br />

following table.<br />

Communication rate Length of bus line Max. no. of<br />

repeaters<br />

9.6 kbps 1200 m 2 126<br />

19,2 kbps 1200 m 2 126<br />

93,75 kbps 1200 m 2 126<br />

187,5 kbps 1000 m 2 126<br />

500 kbps 400 m 4 126<br />

1.5 Mbps 200 m 6 126<br />

12 Mbps 100 m 9 126<br />

Max. no. of nodes<br />

Attention<br />

The maximum number of 32 bus nodes may not be exceeded without a repeater.<br />

D301106 - <strong>BL20</strong>-<strong>ECO</strong> <strong>PROFIBUS</strong>-<strong>DP</strong> 1007 2-3<br />