Parametrization<br />

Table 11:<br />

Gateway<br />

parameters<br />

Byte/<br />

parameter<br />

name<br />

Byte 4:<br />

<strong>–</strong>Bit 6:<br />

Static configuration<br />

0 activate A Changes in the station configuration are stored in the<br />

gateway following a power-on reset.<br />

In case of a module sequence error, a process data<br />

exchange is still possible.<br />

1 deactivate If the static configuration is deactivated, a dynamic<br />

configuration take-over is realized directly following<br />

station configuration changes (important for acyclic<br />

parameterization).<br />

The station stops the process data exchange and the<br />

bus communication as soon as a module sequence error<br />

appears, ignoring the parameterization for error<br />

handling. But, the communication is not interrupted, if<br />

the gateway-parameter byte 1, bit 0 "startup when<br />

expected/actual config. differ" (see page 3-13) is activated.<br />

<strong>–</strong>Bit 7 reserved<br />

Value Meaning<br />

D301106 - <strong>BL20</strong>-<strong>ECO</strong> <strong>PROFIBUS</strong>-<strong>DP</strong> 1007 3-17<br />

3