- Threshold 11.5….14.5 mA<br />
Voltage:<br />
- high signal 15….18 V<br />
- low signal ………7 V max<br />
- Threshold 9.5….12.5 V<br />
Rise <strong>and</strong> fall times: 50 μs max<br />
Evropský sociální fond. Praha & EU: Investujeme do vaší budoucnosti.<br />
Fig. 3.2.5.2: Current/voltage levels in an OpenTherm communication (51)<br />
OpenTherm is not exactly a bus system, because the communication can be only “point-topoint”<br />
or “multipoint-to-point”:<br />
a) An older type of the communication is “point-to-point” (Fig. 3.2.5.3) which means 1<br />
master (controller/thermostat) communicating with 1 slave (boiler).<br />
Fig. 3.2.5.3: Point-to-point communication (51)<br />
b) In June 2008, a new specification version 3.0 came, which brought two innovations:<br />
“Smart power” <strong>and</strong> “multi-point to point” (Fig. 3.2.5.4 <strong>and</strong> Fig. 3.2.5.5)<br />
communication. This means one slave can be controlled by one or more masters. The<br />
heart of this new feature is a special device called “Gateway”, which is placed<br />
between masters <strong>and</strong> a slave (Fig. 3.2.5.4).<br />
Ondřej Nývlt - <strong>Buses</strong>, <strong>Protocols</strong> <strong>and</strong> <strong>Systems</strong> <strong>for</strong> <strong>Home</strong> <strong>and</strong> <strong>Building</strong> <strong>Automation</strong> 35