Cerabar M<br />
operation with Smart<br />
electronics using a<br />
handheld terminal<br />
PROFIBUS-PA Electronics<br />
A Cerabar M with PROFIBUS-PA<br />
electronics has the following operating<br />
options.<br />
• You can set a damping of between 0<br />
and 40 s using communication.<br />
• You can set instrument bus address<br />
direct in the instrument using the<br />
address switch.<br />
Digital display<br />
(optional)<br />
0,753<br />
Smart Electronics Operation Using a<br />
Handheld Terminal<br />
Using the Universal HART<br />
Communicator DXR 275 handheld<br />
terminal, you can set the Cerabar M,<br />
make checks and use additional<br />
functions such as "Damping" and<br />
"Calibration without reference pressure"<br />
all along the 4...20 mA line.<br />
Cerabar M<br />
8<br />
EX EX<br />
• The digital display gives the pressure<br />
as a four-digit number. The bar graph<br />
depicts the current pressure value<br />
related to the measuring range. The<br />
measuring range can be set either on<br />
site using the Zero and Span keys or<br />
remotely using an operating program,<br />
such as Commuwin II.<br />
• Error codes on the digital display and<br />
in Commuwin II simplify error<br />
diagnosis.<br />
Zero Span<br />
1 2 3<br />
on address<br />
off<br />
Display<br />
R<br />
I O<br />
I O<br />
Operating elements<br />
SW<br />
1 2 4 8 16 32 64 HW Value<br />
1 2 3 4 5 6 7 8<br />
DIP switches to set<br />
bus address<br />
Keys for<br />
calibrating the<br />
lower rangevalue<br />
and upper<br />
range-value<br />
1x<br />
minimum line resistance<br />
250 Ω<br />
4...20 mA<br />
2x<br />
1x<br />
2x<br />
Universal HART Comunicator<br />
DXR 275<br />
ON<br />
OFF<br />
Switch No.<br />
Zero Span<br />
Lower rangevalue:<br />
Display<br />
Registration<br />
Upper rangevalue:<br />
Display<br />
Registration<br />
*<br />
* Use an<br />
intrinsically<br />
safe supply<br />
voltage for Ex i<br />
(e.g. RN 221 N)