YLAA Engineering Guide, 180 - Johnson Controls Inc.
YLAA Engineering Guide, 180 - Johnson Controls Inc.
YLAA Engineering Guide, 180 - Johnson Controls Inc.
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Physical Data and Ratings<br />
REFRIGERANT R-410A<br />
<strong>YLAA</strong><br />
STANDARD EFFICIENCY UNITS<br />
FORM 150.72-EG8 (512)<br />
GENERAL UNIT DATA 0<strong>180</strong>SE 0210SE 0240SE 0285SE 0320SE 0360SE 0400SE 0435SE 0485SE<br />
NOMINAL TONS, R-410A1 53.3 57.7 63.2 78.2 87.7 97.6 109.2 118.4 132.1<br />
COP 2.95 2.44 2.7 2.70 2.55 2.65 2.55 2.69 2.56<br />
IPLV 4.58 3.87 4.06 4.27 4.19 4.41 4.29 4.41 4.32<br />
LENGTH (MM) 2911 2911 2911 2949 2949 3690 3690 3690 3690<br />
WIDTH (MM) 2242 2242 2242 2235 2235 2242 2242 2242 2242<br />
HEIGHT (MM) 2508 2508 2508 2393 2393 2393 2393 2393 2393<br />
NUMBER OF REFRIGERANT<br />
CIRCUITS<br />
2 2 2 2 2 2 2 2 2<br />
REFRIGERANT CHARGE, OPERAT-<br />
ING R-410A, CKT 1 / CKT 2, kg<br />
21 / 15 25 / 15 24 / 23 24 / 24 26 / 26 28 / 26 35 / 29 35 / 33 32 / 33<br />
OIL CHARGE, CKT 1 / CKT 2, LITERS 12.0 / 6.0 12.0 / 6.0 12.0 / 6.0 12.6 / 10.4 12.6 / 12.6 18.9 / 12.4 18.9 / 12.6 18.9 / 20.4 18.9 / 18.9<br />
SHIPPING WEIGHT 1668 1702 <strong>180</strong>1 1891 1995 2781 2834 2604 2705<br />
OPERATING WEIGHT<br />
COMPRESSORS, SCROLL TYPE<br />
1689 1723 1821 1916 2028 2814 2873 2642 2755<br />
COMPRESSORS PER CIRCUIT<br />
CONDENSER<br />
3 / 2 2 / 2 2 / 2 2 / 2 2 / 2 3 / 3 3 / 2 3 / 3 3 / 3<br />
TOTAL FACE AREA M2 7.4 7.4 10.0 10.0 10.0 12.6 12.6 15.0 15.0<br />
NUMBER OF ROWS<br />
CONDENSER FANS<br />
1 1 1 1 1 1 1 1 1<br />
NUMBER OF FANS, CKT 1/CKT 2 2 / 2 2 / 2 2 / 2 2 / 2 2 / 2 3 / 2 3 / 2 3 / 3 3 / 3<br />
FAN HP 2 2 2 2 2 2 2 2 2<br />
FAN RPM 950 950 950 950 950 950 950 950 950<br />
TOTAL CHILLER M3 /SEC<br />
EVAPORATOR<br />
19.5 19.5 26 26 26 32.5 32.5 39 39<br />
WATER VOLUME, LITERS 5.4 5.4 5.4 6.7 8.8 8.8 10.0 10.0 13.2<br />
MAXIMUM WATER SIDE PRESSURE,<br />
BAR<br />
10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3<br />
MAXIMUM REFRIGERANT SIDE<br />
PRESSURE, BAR<br />
31 31 31 31 31 31 31 31 31<br />
WATER CONNECTIONS SIZE, INCH 3 3 3 3 3 3 3 3 3<br />
NOTES:<br />
1. Standard Rating Conditions per AHRI Standard 550/590..<br />
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW).<br />
3. Rated in accordance with AHRI Standard 550/590 at an air on condenser temperature of 95°F and a leaving chilled water temperature of 44°F.<br />
4. Additional rating information can be provided by your local <strong>Johnson</strong> <strong>Controls</strong> Sales Office.<br />
14 JOHNSON CONTROLS