8 - Water coIL<br />
8.1 - removing the coil<br />
To remove the coil:<br />
• Remove the unit as described on page 16 and set it<br />
down flat on its side.<br />
• Remove the valves and the water pipes.<br />
• Open the filter access door.<br />
• Remove the filter.<br />
• Remove the coil fixing screws front and rear.<br />
20<br />
Filter access door<br />
coil removal<br />
• Withdraw the bleed valves.<br />
• Remove the nut retaining clips followed by the nuts.<br />
• Withdraw the coil via the filter access door taking care<br />
not to damage the insulation stuck to the sides of the<br />
coil.<br />
• Reverse the procedure described when installing the<br />
replacement coil.<br />
WARNING: Bleed the circuit thoroughly when refilling<br />
the circuit with water.<br />