Electrical Control Valves Series EX4, EX5, EX6, EX7, EX8<br />

Technical Data<br />

Compatibility * HCFCs, HFCs, CO2 Mineral and POE lubricants<br />

MOPD (maximum operating EX4/EX5/EX6/EX7: 35 bar<br />

pressure differential) EX8: 30 bar<br />

Max. working pressure, PS 45 bar<br />

Medium temperature range: Liquid inlet temperature<br />

Uniflow version TS: -50 ... +100°C<br />

Biflow version TS: -40 ... +80°C<br />

Ambient temperature -40 ... +55°C<br />

Storage temperature -40 ... +70°C<br />

CE marking EX4/EX5 not required<br />

EX6/EX7/EX8 required, Cat I, Module A<br />

Salt spray test non-corrosion stainless steel body<br />

Humidity 5 … 95% R.H.<br />

*) Valves are not released for use with inflammable refrigerants.<br />

Block Diagrams<br />

A2.5.1/1003/E<br />

<strong>Alco</strong> <strong>Controls</strong><br />

Superheat Control with EC3-X33 (see page 36) Refrigerant Mass Flow Control with EXD-U (see page 37)<br />

optional display unit ECD-002<br />

1 ECN-N60 sensor<br />

4 PT5 pressure transmitter<br />

6 Supply / Digital Input<br />

9 Alarm out<br />

11 EX4 ... EX8 valve<br />

12 Suction pressure 4..20mA out<br />

13 ECD-002 Display unit<br />

Connections ODF stainless steel fittings<br />

Protection accordance to IP 67 with <strong>Alco</strong> supplied<br />

IEC 529, DIN 40050 cable connector assembly<br />

Vibration for non-connec- 4 g<br />

ted and fastened valve (0 .. 1000 Hz, 1 Oktave /min.)<br />

Shock 20g at 11 ms, 80g at 1 ms<br />

Net weight 0.5 kg (EX4), 0.52 kg (EX5), 0.6 kg (EX6),<br />

1.1 kg (EX7), 1.5 kg (EX8)<br />

Full travel time EX4/EX5/EX6: 1.5 s<br />

EX7: 3.2 s, EX8: 5.2 s<br />

Seat leakage Positive shut-off better than solenoid valve<br />

External leakage ≤ 3 g / Jahr<br />

Package and delivery Single pack,<br />

without electrical connector<br />

24V~<br />

ECP-024<br />

K09-P00<br />

Digital input<br />

EXD-U<br />

0 ... 10V or<br />

4 ... 20mA<br />

EX4<br />

EX5<br />

EX6<br />

EX7<br />

EX8<br />