Conductix-Wampfler Cables for Reeling Systems
Conductix-Wampfler Cables for Reeling Systems
Conductix-Wampfler Cables for Reeling Systems
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Conductix</strong>-<strong>Wampfler</strong> Cable C800<br />
Technical data<br />
Electrical<br />
parameters<br />
Thermal<br />
parameters<br />
Mechanical<br />
parameters<br />
Chemical<br />
parameters<br />
Materials<br />
Design<br />
features<br />
rated voltage UoU = 600/1000V<br />
maximum permitted AC operating voltage UoU = 700/1200V<br />
maximum permitted DC operating voltage UoU = 900/1800V<br />
AC test voltage according to IEC 60502-1<br />
ambient temperature<br />
flexing -10°C to +60°C<br />
fixed -10°C to +60°C<br />
maximum permitted operating temperature at conductor 80°C<br />
short-circuit temperature at conductor 110°C<br />
minimum radii <strong>for</strong> continuous flexing 6 x Ø on spool<br />
tensile load bearing capacity according to data table<br />
combustion behaviour of low flammability according to DIN VDE 0482 part 265-2-1; IEC 60332-1<br />
resistant to ozone no<br />
resistant to humidity yes<br />
UV-resistant yes<br />
resistant to moisture yes<br />
oil resistant yes<br />
halogene free no<br />
insulation special PVC compound<br />
inner sheath special PVC compound<br />
outer sheath special PVC compound<br />
color transparent<br />
conductor flexible copper, category 5 according to DIN VDE 0295 / IEC 60228<br />
conductor coding colored, code norm NFC 32090, CH 7.3, CE 502<br />
Brand <strong>Conductix</strong>-<strong>Wampfler</strong><br />
<strong>Conductix</strong>-<strong>Wampfler</strong> <strong>Cables</strong> <strong>for</strong> Heavy Duty <strong>Reeling</strong><br />
31