■ Overview<br />
The regenerative feedback capability of the PM250 Power Module<br />
in generating mode (electronic braking) means that energy<br />
is returned to the supply system and not destroyed in a braking<br />
resistor. This saves space in the control cabinet, time-consuming<br />
dimensioning of the braking resistor as well as the wiring. Generated<br />
heat is also reduced in the control cabinet.<br />
An innovative circuit design reduces supply harmonics. There is<br />
no need to use an optional line reactor at the supply infeed. This<br />
saves space and costs for engineering and procurement.<br />
The PM250 Power Module is also designed for safety-sensitive<br />
applications. In conjunction with a Safety Control Unit, the drive<br />
can be turned into a Safety Integrated Drive (see Control Units).<br />
© Siemens AG 2007<br />
SINAMICS G120<br />
Inverter chassis units 0.37 kW to 90 kW<br />
PM250 Power Modules<br />
The permissible cable lengths between inverter and motor are<br />
limited depending on cable type. Longer cables can be used if<br />
output reactors are connected (see load-side power components).<br />
For frame size FSC of Power Module PM250 with an integral line<br />
filter of class A, an additional base filter of class B is available for<br />
achieving class B (see line-side power components).<br />
The PM250 Power Modules with integrated line filter to class A<br />
are suitable only for connection to TN supply systems.<br />
Siemens D 11.1 · 2007<br />
3/31<br />
3