DB1 310<br />

PB100511_SE-30<br />

PB100513_SE-30<br />

Protection<br />

Circuit protection<br />

ABS<br />

DNV<br />

LRS RMRoS<br />

BV GL<br />

RINA<br />

<strong>C60L</strong> 1P <strong>C60L</strong> 2P<br />

<strong>C60L</strong> 3P <strong>C60L</strong> 4P<br />

PB10051 _SE-30<br />

PB100514_SE-30<br />

KRS<br />

<strong>Marine</strong> <strong>C60L</strong> <strong>circuit</strong> <strong>breakers</strong><br />

(<strong>curve</strong> C)<br />

IEC/EN 60947-2<br />

<strong>Marine</strong> approvals<br />

b <strong>Schneider</strong> <strong>Electric</strong> is committing to have all products <strong>Marine</strong> type approved by<br />

IACS (International Association of Classification Societies):<br />

v ABS, BV, DNV, GL, KRS, LRS, RINA, RMRoS and meet international standards<br />

requirements that are compulsory for the worldwide merchant marine market,<br />

v other classification bodies: please consult us.<br />

b <strong>C60L</strong> <strong>circuit</strong> <strong>breakers</strong> are <strong>circuit</strong> <strong>breakers</strong> which combine the following functions:<br />

v <strong>circuit</strong> protection against short-<strong>circuit</strong> currents,<br />

v <strong>circuit</strong> protection against overload currents,<br />

v breaking and industrial disconnection as per standards IEC/EN 60947- .<br />

b The presence of the green strip guarantees physical opening of the contacts and<br />

allows operations to be performed on the downstream <strong>circuit</strong> in complete safety.<br />

b Increased product service life thanks:<br />

v overvoltage resistance,<br />

v high performance limitation,<br />

v to fast closing independent of the speed of actuation of the toggle.<br />

b Upstream or downstream connection.<br />

Positive contact indication<br />

b Suitability for isolation in accordance with the IEC/EN 60947- standard.<br />

Alternating current (AC) 50/60 Hz<br />

Ultimate breaking capacity (Icu) as per IEC/EN 60947-2 Service<br />

Voltage (Ue)<br />

breaking<br />

Ph/Ph (2P, 3P, 4P)<br />

Ph/N (1P)<br />

240 V<br />

-<br />

415 V<br />

240 V<br />

-<br />

415 V<br />

440 V<br />

-<br />

capacity<br />

(Ics)<br />

Rating (In) 0.5 to 5 A 50 kA 5 kA 6 kA 0 kA 50 % of Icu<br />

i IT<br />

1. x 1 In<br />

Catalogue numbers<br />

<strong>Marine</strong> <strong>C60L</strong> <strong>circuit</strong> breaker<br />

Type 1P 2P 3P 4P<br />

1<br />

2<br />

Rating (In) Curve C Curve C Curve C Curve C<br />

0.5 A 25406 25407 25408 25409<br />

1 A 25392 25418 25431 25444<br />

A 25393 25419 25432 25445<br />

3 A 25394 25420 25433 25446<br />

4 A 25395 25421 25434 25447<br />

6 A 25396 25422 25435 25448<br />

10 A 25397 25423 25436 25449<br />

16 A 25398 25424 25437 25450<br />

0 A 25399 25425 25438 25451<br />

5 A 25310 25426 25439 25452<br />

Width in 9-mm modules 4 6 8<br />

1<br />

2<br />

version: 1.1 CM901013E.indd<br />

3<br />

4<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8


DB118767<br />

Protection<br />

Circuit protection<br />

DB11877 Clip on DIN rail 35 mm.<br />

Indifferent position of installation.<br />

DB1 3103<br />

DB1 577<br />

<strong>Marine</strong> <strong>C60L</strong> <strong>circuit</strong> <strong>breakers</strong><br />

(<strong>curve</strong> C) (cont.)<br />

Connection<br />

Technical data<br />

According to IEC/EN 60947-2<br />

Insulation voltage (Ui) 500 V AC<br />

Pollution degree 3<br />

Rated impulse withstand voltage (Uimp) 6 kV<br />

Thermal tripping Nominal temperature<br />

for operation<br />

50 °C<br />

According to ambiant<br />

temperature<br />

See module 9 515<br />

Magnetic tripping (Ii) C <strong>curve</strong> 8.5 In ± 0 %<br />

According to current<br />

frequency<br />

50/60 Hz<br />

Utilization category A<br />

Compliance with IACS part E10<br />

Other characteristics<br />

Degree of protection Device in modular<br />

enclosure<br />

IP40<br />

Endurance (O-F) <strong>Electric</strong>al 10,000 cycles<br />

Weight (g)<br />

14 mm<br />

5.5 mm<br />

PZ<br />

Circuit-breaker<br />

Type <strong>C60L</strong><br />

1P 1 0<br />

P 40<br />

3P 360<br />

4P 480<br />

Dimensions (mm)<br />

Rating Tightening<br />

torque<br />

Mechanical 0,000 cycles<br />

Service temperature -30°C to +70°C<br />

Storage temperature -40°C to +80°C<br />

Power loss See module 9 517<br />

Connection Upstream or downstream<br />

Copper cables<br />

Rigid Flexible or<br />

with ferrule<br />

0.5 to 5 A N.m 1 to 5 mm 1 to 5 mm<br />