02.02.2013 Views

PolyGard® Gas Controller MGC-02 - Imbema Belgium

PolyGard® Gas Controller MGC-02 - Imbema Belgium

PolyGard® Gas Controller MGC-02 - Imbema Belgium

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

PolyGard ® <strong>Gas</strong> <strong>Controller</strong> <strong>MGC</strong>-<strong>02</strong><br />

Description<br />

<strong>Gas</strong> measuring controller series for continuous<br />

monitoring and warning of toxic, combustible and<br />

refrigerant gases and vapours.<br />

The <strong>Gas</strong> <strong>Controller</strong> series <strong>MGC</strong>-<strong>02</strong> can monitor up to 24<br />

analog gas transmitters with 4 to 20 mA signal. Five<br />

alarm thresholds are adjustable to each channel. For<br />

activating the alarm up to 20 relays with changeover<br />

contacts are available.<br />

The free adjustable parameters and alarm threshold<br />

enable a very flexible use in the gas measuring<br />

technique. Simple and comfortable commissioning is<br />

granted by the factory adjusted parameters.<br />

The configuration, parameter settings and operation is<br />

easy to do without programming knowledge.<br />

The <strong>Gas</strong> <strong>Controller</strong> <strong>MGC</strong>-<strong>02</strong> is equipped with a self<br />

monitoring system and with a power supply monitoring.<br />

The analog inputs are monitored to detect short-circuit<br />

and wire break.<br />

Optionally the gas controller has got a serial interface.<br />

Additionally the gas controller is available with<br />

emergency power supply.<br />

Application<br />

The <strong>MGC</strong>-<strong>02</strong> gas controller is used for monitoring and<br />

warning of toxic and combustible gases as well as of<br />

Freon refrigerant.<br />

The <strong>MGC</strong>-<strong>02</strong> gas controller fulfills the functions of<br />

monitoring Carbon monoxide (CO) in garages and<br />

tunnels etc. in accordance with VDI 2053 and ÖNORM.<br />

Additionally ammonia (NH3)- refrigerant plants can be<br />

monitored in accordance with the requirements EN 378,<br />

VBG 20 and with the guidelines "safety-relevant<br />

requirements for ammonia refrigeration systems".<br />

Due to free configurable parameters and alarm<br />

thresholds the <strong>MGC</strong>-<strong>02</strong> gas controller is suitable for<br />

various applications in the range of gas measurement<br />

and monitoring.<br />

December 06 PolyGard ® is a registered trademark of MSR electronic 1<br />

MSR electronic GmbH | Würdinger Straße 27 | D 94060 Pocking<br />

Phone: +49 (0) 85 31 – 90 04 0 | Fax: +49 (0) 85 31 – 90 04 54 Specification subject to change without notice


Features<br />

� Up to 24 analog inputs, 4 to 20 mA to one controller<br />

� For larger Projects cascadable max. three controllers (72 analog inputs)<br />

� For monitoring CO, CO2, NO, NO2, NH3, O2, SO2, H2S, CL2, ETO, combustible and<br />

refrigerant gases<br />

� Simple and comfortable commissioning due to configuration with standard parameter<br />

� Logical system menu in different languages<br />

� Flexible configuration by programmable parameters<br />

� Five adjustable alarm thresholds for each channel<br />

� Up to 20 relay with SPDT, potentialfree, max. 250 VAC, 5A.<br />

� Failure relay with SPDT, potentialfree, max. 250 VAC, 5A<br />

� Twelve analog outputs, 4 mA to 20 mA<br />

� Conform to VDI - 2053<br />

� Shapely, durable housing<br />

� Housing lockable (optional)<br />

� Serial interface (optional)<br />

� Emergency power supply (optional)<br />

� Power fail flashing light (optional)<br />

� Integrated buzzer (optional)<br />

December 06 PolyGard ® is a registered trademark of MSR electronic 2<br />

MSR electronic GmbH | Würdinger Straße 27 | D 94060 Pocking<br />

Phone: +49 (0) 85 31 – 90 04 0 | Fax: +49 (0) 85 31 – 90 04 54 Specification subject to change without notice


Specifications<br />

Electrical<br />

Power supply<br />

Power consumption (inkl. max. AT)<br />

<strong>MGC</strong>-<strong>02</strong>-04-04<br />

<strong>MGC</strong>-<strong>02</strong>-08-08 to <strong>MGC</strong>-<strong>02</strong>-12-12<br />

<strong>MGC</strong>-<strong>02</strong>-16-16 to <strong>MGC</strong>-<strong>02</strong>-24-16<br />

110/230 VAC 50/60Hz;<br />

24 VAC/DC -10% + 20%<br />

13 W, 500 mA<br />

27 W, 1100 mA<br />

55 W, 2200 mA<br />

Option Emergency power supply Supply duration 60 minutes<br />

Analog input (max. 24)<br />

4 to 20 mA, overload- and short-circuitprotected,<br />

input resistor 200 Ω<br />

Power supply for external analog transmitters 24 VDC max. 50 mA / channel<br />

Analog output (max 12, 2 each module), 4 to 20 mA, overload- and short-circuit-<br />

Free adjustable to each channel.<br />

protected, max. 500 Ω load<br />

Alarm relay (max. 20) 250 VAC, 5 A, potential free, SPDT<br />

Failure relay (1) 250 VAC, 5 A, potential free, SPDT<br />

Option buzzer - Acoustic pressure 85 dB (Distance 300 mm)<br />

- Frequency<br />

Visualization<br />

3,5 kHz<br />

Display Two lines, each 16 characters, illumination.<br />

Status LED Yellow = Status Alarm; Red = Failure<br />

Operation<br />

<strong>Gas</strong>es<br />

6 Push button<br />

1<br />

<strong>Gas</strong> Transmitter external<br />

CO, CO2, NO, NO2, NH3, O2, SO2, H2S, CL2,<br />

ETO, combustible gases and Freons<br />

Environmental<br />

Humidity 15 – 95 % RH non-condensing<br />

Working temperature -10 °C to + 50 °C (14 °F to 122 °F)<br />

Storage temperature 0 °C to + 50 °C (32 °F to 122 °F)<br />

Physical<br />

Enclosure Plastic housing with transparent cover<br />

Color RAL 7035 (gray)<br />

Protection class IP 65<br />

Weight 2 <strong>MGC</strong>-<strong>02</strong>-04-04<br />

<strong>MGC</strong>-<strong>02</strong>-08-08 to <strong>MGC</strong>-<strong>02</strong>-12-12<br />

<strong>MGC</strong>-<strong>02</strong>-16-16 to <strong>MGC</strong>-<strong>02</strong>-20-16<br />

<strong>MGC</strong>-<strong>02</strong>-24-16<br />

2,7 kg (6.0 Ibs.)<br />

4,0 kg (9.0 Ibs.)<br />

6,0 kg (13.5 Ibs.)<br />

7,5 kg (16.5 Ibs.)<br />

Mounting Wall mounting<br />

Cable entry M 16; M 20; M 25<br />

Wire connection: Power supply<br />

Screw type: 2,5 mm<br />

Relay<br />

Input<br />

2 (14 AWG)<br />

Spring type: 0,5 to 1,5 mm 2 (22 to 16 AWG)<br />

Spring type: 0,5 to 1,5 mm 2 (22 to 16 AWG)<br />

Dimensions 2 (W x H x D) <strong>MGC</strong>-<strong>02</strong>-04-04 298 x 260 x 140 mm (11.7 x 10.2 x 5.5 in.)<br />

<strong>MGC</strong>-<strong>02</strong>-08-08 to <strong>MGC</strong>-<strong>02</strong>-12-12 298 x 420 x 140 mm (11.7 x 16.5 x 5.5 in.)<br />

<strong>MGC</strong>-<strong>02</strong>-16-16 to <strong>MGC</strong>-<strong>02</strong>-20-16 298 x 570 x 140 mm (11.7 x 22.5 x 5.5 in.)<br />

<strong>MGC</strong>-<strong>02</strong>-24-16<br />

410 x 655 x 140 mm (16.1 x 25.8 x 5.5 in.)<br />

EMV – Guidelines 89/336/EWG; CE<br />

Guidelines<br />

Low voltage guideline 73/23/EWG<br />

VDI 2053<br />

Warranty One year on material and workmanship<br />

1 2<br />

Other gases on request Data for plastic enclosure<br />

December 06 PolyGard ® is a registered trademark of MSR electronic 3<br />

MSR electronic GmbH | Würdinger Straße 27 | D 94060 Pocking<br />

Phone: +49 (0) 85 31 – 90 04 0 | Fax: +49 (0) 85 31 – 90 04 54 Specification subject to change without notice


Order Information<br />

<strong>MGC</strong>-<strong>02</strong>-00-00-00000<br />

Example: <strong>MGC</strong>-<strong>02</strong> with 12 measuring points, 15 relays, Language English, buzzer.<br />

Order No. <strong>MGC</strong>-<strong>02</strong>-12-12-00011<br />

Connecting diagram<br />

(Example <strong>MGC</strong>-<strong>02</strong>-04-04)<br />

1<br />

2<br />

+24V<br />

0V<br />

Power supply<br />

110 to 230 VAC<br />

+24V<br />

0V<br />

+<br />

-<br />

Power<br />

Option<br />

1XXXX Emergency power supply<br />

X1XXX Power fail flashing light<br />

XXX1X Integrated buzzer<br />

XX1XX Housing lockable<br />

XXXX0 Language German<br />

XXXX1 Language English<br />

XXXX2 Language USA<br />

XXXX3 Language Netherlands<br />

XXXX4 Language Danish<br />

XXXX5 Language Czech<br />

Version<br />

04-04 04 Measuring point, 05 Relay<br />

08-08 08 Measuring point, 10 Relay<br />

12-12 12 Measuring point, 15 Relay<br />

16-16 16 Measuring point, 20 Relay<br />

20-16 20 Measuring point, 20 Relay<br />

24-16 24 Measuring point, 20 Relay<br />

Relay<br />

R 01<br />

Relay<br />

R <strong>02</strong><br />

Relay<br />

R 03<br />

D1 D2 D3 D4 D5<br />

digital output<br />

<strong>Gas</strong> <strong>Controller</strong> <strong>MGC</strong> <strong>02</strong><br />

Bus_A<br />

Bus_B<br />

Relay<br />

R 04<br />

+ DI 01<br />

+ DI <strong>02</strong><br />

+ DI 03<br />

+ DI 04<br />

-<br />

-<br />

Relay<br />

R 05<br />

X1 1 2 X2 1 2 3 4 5 6 X2 7 8 9101112131415<br />

> 4-20 mA<br />

< 24 VDC<br />

GND<br />

> 4-20 mA<br />

< 24 VDC<br />

analog input<br />

Enclosure<br />

0X Plastic Enclosure (Standard)<br />

1 X Metal Enclosure<br />

> 4-20 mA<br />

< 24 VDC<br />

GND<br />

> 4-20 mA<br />

< 24 VDC<br />

MP01 MP<strong>02</strong> MP03 MP04<br />

analog<br />

output<br />

+ AO 01<br />

-<br />

+ AO <strong>02</strong><br />

< 4-20 mA<br />

> GND<br />

< 4-20 mA<br />

System<br />

Bus<br />

December 06 PolyGard ® is a registered trademark of MSR electronic 4<br />

MSR electronic GmbH | Würdinger Straße 27 | D 94060 Pocking<br />

Phone: +49 (0) 85 31 – 90 04 0 | Fax: +49 (0) 85 31 – 90 04 54 Specification subject to change without notice<br />

digital<br />

input<br />

SCL<br />

SDA<br />

GND<br />

PE NL<br />

110 - 230<br />

VAC<br />

X10 1 2 3 4 5 6 7 8 9101112 X11 1 2 3 4 5 6 7 8 9 10 1112<br />

System<br />

Bus