General General General description<br />
description<br />
description<br />
The units described in this manual are not built according to ATEX Directive (Explosive atmosphere).<br />
The liquid chillers of “ip” range have been made to meet the needs of industrial processes or plants where the production of<br />
chilled water is required. A variety of models and powers are available to cover a vast range of applications, with inlet water<br />
temperatures between +20°C and 0°C.<br />
Cold water is produced through a refrigerant cycle, as shown in the diagram given later in this <strong>catalogue</strong>.<br />
Benefits Benefits<br />
Benefits<br />
- “NO “NO-FROST”<br />
“NO FROST” Evaporator<br />
After freezing-up, the performances do not get worse and the water doesn’t<br />
pollute the refrigerant circuit;<br />
- High High C.O.P.<br />
C.O.P.<br />
- Resistant metal works with compressor separation wall<br />
wall<br />
<strong>Technical</strong> <strong>Technical</strong> specifications<br />
specifications<br />
Metal Metal Metal works works (mod. (mod. M2 M2 - M4 M4 - M6)<br />
M6)<br />
METAL METAL WORKS WORKS in galvanized sheet steel, stove-enamelled<br />
with polyurethane powders and is equipped with bearing<br />
foot, for fixed installation.<br />
Metal Metal works works (mod. (mod. 10 10 ÷ ÷ 1402)<br />
1402)<br />
METAL METAL WORKS WORKS in galvanized sheet steel, stove-enamelled<br />
with polyurethane powders and is equipped with bearing<br />
foot, for fixed installation.<br />
BASE BASE FRAME FRAME in galvanized sheet steel, stove-enamelled<br />
with polyurethane powders and is equipped with bearing<br />
foot, for fixed installation.<br />
INTERNAL INTERNAL INTERNAL METAL METAL WORKS WORKS in galvanized sheet steel.<br />
DRIP DRIP TRAY TRAY for rain water collection in case of outside<br />
installation, complete with type discharge fitting connectable<br />
without disassembling any panel.<br />
FRAME FRAME is made in anodized aluminium profiles, using<br />
aluminium-alloy angle-joints.<br />
PANELS PANELS in galvanized steel, externally coated with PVC<br />
film. Fastening to aluminium frame by stainless steel<br />
screws, fitted on panel’s edge.<br />
AIR AIR-TIGHT AIR TIGHT GASKETS GASKETS on panels’ edges, made in<br />
polyurethane with dual density (Models Micro2 – Micro4 not<br />
included).<br />
Fans Fans section section<br />
section<br />
EUROKLIMAT EUROKLIMAT Spa Spa<br />
IPE2008_2.0_uk 3<br />
IP IPE IP<br />
AXIAL AXIAL FAN(S) FAN(S) directly coupled to the electric motor, 4 or 6<br />
poles, external rotor type, with special labyrinth watertight,<br />
bearings free from servicing and incorporated thermal<br />
protection. Fans have blades with haul profile, dinamically<br />
and statically balanced and are equipped with accident<br />
prevention grill on air inlet.<br />
Refrigerant Refrigerant circuit circuit<br />
circuit<br />
Refrigerant circuit is completely made in braze welded<br />
copper tube with silver alloy and is insulated on suction part,<br />
to avoid creation of condensate. It is complete with safety<br />
device. For models 502 502 and 1402 1402 the circuit is double and<br />
completely independent. It is mainly composed by:<br />
“ROTATIVE” ROTATIVE” HERMETIC HERMETIC COMPRESSOR<br />
COMPRESSOR, COMPRESSOR for models M2 –<br />
M4 M4 – M6 M6, M6<br />
fitted on antivibration mountings. Electrical motor<br />
is cooled by refrigerant suction gas and is protected against<br />
working anomalies by thermistors embedded in windings.<br />
HERMETIC HERMETIC HERMETIC COMPRE COMPRESSOR COMPRE COMPRESSOR<br />
SSOR ”SCROLL”TYPE ”SCROLL”TYPE for models<br />
from 10 to 201 included, safety valve between suction and<br />
inlet. Electrical motor is cooled by refrigerant suction gas<br />
and is protected against working anomalies by thermistors<br />
embedded in windings for models up to the 81 81 included and<br />
integral electronic protection for models from 101 101 to<br />
201 201.They 201 are fitted on antivibration mountings.