7. PROTECTION AGAINST EXCESS TEMPERATURES. SAFETY VALVES.<br />
<strong>OKSOL</strong>-<strong>150</strong> integrates the safety devices required in a solar system.<br />
. Primary or solar circuit: A 3 bar safety valve guarantees<br />
safety and correct system operation.<br />
. Absorber design assumes solar fluid dilation of up to<br />
1.2 litres. As a consequence pressure fluctuation inside<br />
the absorber is minimal.<br />
PRIMARY DRAIN OUTLET<br />
We recommend covering the collector during prolonged absence of DHW<br />
consumption during low consumption periods (summer, etc.). The tank<br />
should not be drained. Do not close the inlet valve (each time the water<br />
reaches the maximum temp. A certain amount of water will be drained,<br />
which will be replaced by tap water at a lower temp.).<br />
The collector can be covered with an opaque and safe tarp, to prevent<br />
solar radiation acting on it.<br />
. DHW circuit: A 6 bar pressure and 95ºC safety valve<br />
guarantees optimum service range.<br />
SECONDARY DRAIN OUTLET<br />
SECONDARY INLET<br />
8.<br />
ANTI-FREEZE PROTECTION<br />
<strong>OKSOL</strong>-<strong>150</strong> STRUCTURE: 30-40<br />
Solar circuit<br />
The solar circuit heat transfer fluid contains a percentage of glycol, which varies depending on the weather at the system location. This percentage is<br />
established as a function of the historical minimum for the area and therefore the circuit is protected against freezing. The anti-freeze fluid sheet should<br />
clearly reflect the glycol-water mixture minimum operating temperature.<br />
The primary circuit is loaded ready for the customer with a concentration of 50% propylene glycol, which guarantees a freezing point below 35°C (see<br />
item 14).<br />
DHW circuit<br />
For extreme climate areas <strong>Orkli</strong> has designed an anti-freeze kit. Please contact our technicians for further information about this device.<br />
In the event of a prolonged absence, empty the solar accumulator (see chapter "Accumulator Drainage").<br />
Freezing trials carried out with the system in CENIFER refrigerator laboratories show that at rest and at a water temp. in the initial tank of 13 º C, the<br />
system remains above freezing point more than three consecutive days at -10 º C, without any sunlight.<br />
Chamber Temp. [Cº] Start Temp [Cº] End Temp. [Cº] Time [hours]<br />
-20 13 0.2<br />
37:25<br />
-10 13<br />
0.2<br />
77:00<br />
In case of freezing, the system itself with minimum radiation, undertakes to defrost the tank water<br />
9.<br />
LIGHTNING PROTECTION<br />
We recommend that a copper cable with a diameter of at least 16 mm2 should be used to connect to the lightning arrest system of the building.<br />