TERMOSUPREMA Compact - DSA
TERMOSUPREMA Compact - DSA
TERMOSUPREMA Compact - DSA
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Thermocooker – <strong>TERMOSUPREMA</strong> <strong>Compact</strong> <strong>DSA</strong><br />
50 cm<br />
(1) If there are flues which are side by side, one<br />
chimney pot must surpass the other by at least 50<br />
cm in order to avoid pressure transfers between the<br />
flues themselves.<br />
Picture 7<br />
2 m 10 m<br />
1<br />
m<br />
(1) The chimney pot must not have obstacles within 10 m such<br />
as walls, slopes or trees. If this is not the case, raise the pot by<br />
at least 1 m above the obstacle.<br />
The chimney pot must surpass the roof ridge by at least 1 m.<br />
Picture 8<br />
> _ A<br />
>A<br />
0.5 m<br />
min. H<br />
(1)Ridge axis<br />
α<br />
(2)Roof<br />
Picture 9<br />
CHIMNEY POT DISTANCES AND POSITIONING: UNI 10683/98<br />
Roof slope<br />
Distance between ridge and<br />
chimney<br />
Minimum chimney height (measured from the<br />
outlet)<br />
α A (m) H (m)<br />
15°<br />
30°<br />
45°<br />
60°<br />
< 1.85 m 0.50 m beyond the ridge<br />
> 1.85 m 1.00 m from the roof<br />
< 1.50 m 0.50 m beyond the ridge<br />
> 1.50 m 1.30 m from the roof<br />
< 1.30 m 0.50 m beyond the ridge<br />
> 1.30 m 2.00 m from the roof<br />
< 1.20 m 0.50 m beyond the ridge<br />
> 1.20 m 2.60 m from the roof<br />
28 Instructions for installation, use and maintenance – EN – Rev.00