This project encompasses a redevelopment plan for one of the vacant office buildings in Heerlen. It is the graduation project of the Bachelor Built Environment at Zuyd University of applied science (Dutch). The goal was to redevelop the building from an office into apartments and studios focused specifically on young one person households, while also adding quality green space to Heerlens city center.
This project encompasses a redevelopment plan for one of the vacant office buildings in Heerlen. It is the graduation project of the Bachelor Built Environment at Zuyd University of applied science (Dutch). The goal was to redevelop the building from an office into apartments and studios focused specifically on young one person households, while also adding quality green space to Heerlens city center.
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
5.2 – Energie
Een van de eisen aan het projectgebouw is dat het
energieneutraal wordt uitgevoerd. Dit houd in dat er
minstens even veel energie wordt opgewekt als er gebruikt
wordt in het pand. Om het pand energieneutraal te maken
zijn energieberekeningen uitgevoerd. De uitwerking van deze
berekeningen vind u verderop in deze paragraaf. Daarnaast
is een EPC berekening uitgevoerd aan de hand van Uniec.
De resultaten van de EPC berekening zijn opgenomen in
bijlage 4. De EPC berekening gaat enkel over bouwdeel A.
5.2.1 – Berekening zonenergie
Een klein huishouden verbruikt gemiddeld 1930 kWh/jaar.
Deze waarde gaat echter uit van een huishouden waarin de
ruimteverwarming en warm tapwater bereiding met gas
voldaan worden. Omdat het gebouw beter geïsoleerd is dan
de gemiddelde woning (ie bijlage 3 voor een berekening)
wordt er minder energie gebruikt en kan worden
aangenomen dat de nodige energie voor ruimteverwarming
en warm tapwater bereiding gecompenseerd wordt door de
besparing. (Milieu Centraal, 2018) Voor kantoren wordt
gerekend met een energieverbruik van 109 kWh/m 2 en voor
horeca wordt gerekend met een energieverbruik van 120
kWh/m 2 . deze cijfers komen voort uit een rapport van
SenterNovum. (SenterNovum, 2007)
Voor de opwekking van energie wordt uitgegaan van een
gemiddelde opbrengst van 100 kWh/m 2 voor de
zonnepanelen die op het dak liggen. (Energieleveranciers,
2018) Voor de ZigZagSolar wand wordt uitgegaan van een
optimale opbrengst van 135 kWh/m 2 geveloppervlakte
conform informatie van de leverancier. (Wall, 2018)
Energieverbruik:
Woningen: 1930 kWh/jaar * 19 = 36.670 kWh/jaar
Kantoren: 109 kWh * 285 m 2 = 31.065 kWh/jaar
Horeca: 120 kWh * 112 m 2 = 13.440 kWh/jaar
----------------------- +
81.175 kWh/jaar
De woningen gebruiken 45,17% van alle energie. Enkel de
woningen in bouwdeel A (15 woningen) gebruiken 35.66%
van alle energie. In de EPC berekening is dan ook slechts
35,66% van de energieleverende toepassingen meegenomen.
Energieopwekking:
Dakoppervlak zonnepanelen:
Dak A: 12,8*23,1= 295,7 m 2
Dak C: 11,2*31,7= 355,1 m 2
---------------- +
650,8 m 2
650,8 m 2 * 100 kWh/m 2 = 65.080 kWh/jaar
ZigZagSolar wand:
11,45 * 11,22 = 128,5 m 2
128,5 m 2 * 135 kWh/m 2 = 17.347 kWh/jaar
Totaal:
66.560 + 12.850 = 82.427 kWh/jaar
Ten behoeve van de EPC berekening voor bouwdeel A wordt
uitgegaan van 35.66 % van de energieopwekking. Dit om de
berekening in verhouding kloppend te maken. Toepassing
van dit percentage resulteert in de volgende cijfers:
Totaal dakoppervlak:
650,8 m 2 * 35,66% = 232,08 m 2
128,5 m 2 * 35,66% = 45,82 m 2
5.2.2 – Daglicht & zontoetreding
De woningen hebben allemaal een klein raam in de
badkamer en ten minste drie ramen in het woongedeelte. In
bijlage 2 is een daglichttoetreding te vinden met betrekking
op woningtype 1C. Verder is meer informatie over de
berekening te vinden in hoofdstuk 7.2. De ramen zijn
voorzien van geïntegreerde zonneschermen aan de
buitenkant die dient als zonwering.
5.2.3 – Verwarming & koeling
Voor ruimteverwarming en koeling wordt gebruik gemaakt
van een all-electric systeem. De ruimte verwarming en
koeling vind plaats met behulp van een warmtepomp die
wordt aangesloten op het lokale mijnwatersysteem. Door
gebruik te maken van een elektrische warmtepomp in plaats
van een elektrische cv ketel kan een rendement van 400%
gehaald worden. Door de warmtepomp ook te gebruiken
voor koeling wordt de warmtebron geregenereerd waardoor
deze in de winter weer warm genoeg is om de woning in
warmte te voorzien.
5.2.4 – Ventilatie
De woningen in bouwdeel A en C worden geventileerd door
middel van een natuurlijke luchttoevoer via de in de woning
gelegen gevelopeningen. De toegevoerde lucht wordt door
een mechanische afvoer in de keuken en badkamer de
woning uitgevoerd. Dit zelfde principe geld voor de horeca
gelegenheid in bouwdeel C. De ventilatielucht in bouwdeel B
wordt aangevoerd via roosters in de vloer. De koele lucht
warmt op en stijgt naar het plafond, waar de lucht via een
mechanische afzuiging weggevoerd wordt via het dak.
5.2.5 – Verlichting en armatuur
De energievraag voor verlichting en armatuur is gebaseerd
op kengetallen uit de EPC berekening (bijlage 4). Hieruit
blijkt dat 46863 MJ nodig is om bouwdeel A van energie te
voorzien. Deze waarde is forfaitair bepaald en kan daarom
in praktijk lager uitpakken. In de gezamenlijke delen van
het gebouw word LED verlichting toegepast. Daarnaast is er
zoveel mogelijk gekozen voor low-tech ingrepen zoals
natuurlijke ventilatie.
31